OWNERS SERVICE MANUAL

NO. 05605

INSTALLATION, OPERATING & SERVICING INSTRUCTIONS

Wheeled

Models 450, 451, 452 ( 25 Cu. Ft. Nitrogen Cylinder 16” wheels)
Models 467, 468, 469 (110 Cu. Ft. Nitrogen Cylinder 16” wheels)
Models 470, 471, 472 (110 Cu. Ft. Nitrogen Cylinder 36” wheels)
Stationary
Models 481, 482, 483 ( 23 Cu. Ft. Nitrogen Cylinder)
Models 484, 485, 486 (110 Cu. Ft. Nitrogen Cylinder)




































All fire extinguishers should be installed, inspected and maintained in
accordance with the National Fire Protection Association standard titled
"Portable Fire Extinguishers", NFPA-10 and the requirements of local
authorities having jurisdiction.

When maintenance is indicated it should be performed by trained
persons having proper equipment. Fire extinguishers are pressure
vessels and must be treated with respect and handled with care. They
are mechanical devices and require periodic maintenance to be sure that
they are ready to operate properly and safely. Amerex strongly
recommends that the maintenance of portable fire extinguishers be done
by a trained professional – your local authorized Amerex Distributor.

Amerex Corporation makes original factory parts available to insure
proper maintenance – USE OF SUBSTITUTE PARTS RELEASES
AMEREX OF ITS WARRANTY OBLIGATIONS. Amerex parts have
machined surfaces and threads that are manufactured to exacting
tolerances. O-rings, hoses, nozzles, and all metal parts meet precise
specifications and are subjected to multiple in-house inspections and
tests for acceptability. There are substitute parts available that may be
incorrectly labeled as UL component parts, some are advertised as
Amerex type. None of these meet UL requirements and all of them void
the Amerex extinguisher warranty and UL listing. DO NOT
SUBSTITUTE.

RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE

REFERENCES IN THIS MANUAL:

AVAILABLE FROM:

NFPA-10 Portable Fire Extinguishers

National Fire Protection Association

1 Batterymarch Park, P.O, Box 9101

Quincy, MA 02269-9101

CGA C-1 Methods for Hydrostatic Testing of

Compressed Gas Association, Inc.

Compressed Gas Cylinders

4221 Walney Road, 5

th

Floor

CGA C-6 Standard for Visual Inspection of

Chantilly, VA 20151-2923

Compressed Gas Cylinders

AMEREX CORPORATION – P.O. BOX 81 – TRUSSVILLE, ALABAMA 35173-0081

Phone: 205/655-3271 Fax: 800/654-5980

e-mail:

[email protected]

Web Page:

http://www.amerex-fire.com

Printed in U.S.A.

0M05605H Rev.10/11

1

2

5

/1

5

0

L

B

.

NI

T

R

O

G

E

N

CY

L

IN

DE

R

O

P

E

R

AT

E

D

D

RY

C

HE

M

IC

AL

F

IRE

E

X

T

IN

G

U

IS

H

E

R

S

Advertising