TROUBLESHOOTING GUIDE


WARNING:

BEFORE ATTEMPTING TO CORRECT ANY LEAKAGE PROBLEM, BE SURE THAT

THE AGENT CYLINDER IS COMPLETELY DEPRESSURIZED. Always use caution when opening
the shutoff nozzle or any other connection as a leaking nitrogen cylinder valve seat may have
pressurized the agent container refer to the recharge procedure for proper method of
depressurization.

PROBLEM

CORRECTIVE ACTION

1.

Nitrogen

cylinder gauge

reads low or high

Temperature may have affected the pressure reading

Temperature (F)

35º

70º

120º

Temperature (C)

21º

49º

Recommended Pressure

psig

1880 2015 2200

mPa

13.0

13.9

15.2

Minimum Pressure

psig

1590 1700 1900

mPa

11.0

11.7

13.1


NO CORRECTIVE ACTION IS REQUIRED IF THE
PRESSURE IS WITHIN PARAMETERS STATED ABOVE.

2.

Nitrogen pressure is too low.
Valve is closed. Tamper seal
is intact. There is pressure in
the agent and nitrogen
cylinders.

Valve seat has leaked and has pressurized the agent
cylinder. Follow Recharge Procedure for restoring the
extinguisher to service.

3.

Nitrogen pressure is too low.
Valve is closed. Tamper seal
is intact. No pressure
observed in the agent
cylinder.

Leakage in the nitrogen valve at other than the valve seal.
Replace with a properly charged nitrogen cylinder.

4.

Shutoff nozzle does not move
freely.

Disassemble, clean and lubricate.

5.

Unable to remove the agent
cylinder cap.

Agent cylinder may be pressurized. Make no further attempt
to remove the cap until this is checked. See the Recharge
Procedure for proper depressurization method.

6.

Nitrogen hose cut, cracked or
abraded.

Replace hose assembly.

7.

Chemical agent and pressure
leaking from the safety disc
assembly. (Models 450, 451,
452)

Inspect safety outlet for tightness or damage. Tighten if
necessary.

NOTE: Only tighten the large hex nut of the assembly. The
small round nut containing the holes is factory set to a
specific torque value. Do not attempt to adjust. If damaged
or ruptured, replace complete Amerex Safety Disc
Assembly.