Models 891 and 892

– 80 and 200 lb. Halotron I Bulk Recharge Cylinders

1. Connect the argon supply hose to the vapor valve on the leaking supply cylinder and

maintain a constant argon pressure of 100 psig (689 kPa) throughout the transfer.

2. Connect the recharge hose assembly to the liquid supply on the leaking cylinder to

the liquid supply on a new cylinder that is under a vacuum.

3. Open the liquid valves on both cylinders to allow the liquid to transfer into the new

cylinder.

4. When the liquid transfer is complete, allow the cylinders to equalize pressure at 100

psig (689 kPa) before closing the liquid valves and venting the hose.