Oil smart, Water pump switch – Blue Angel Pumps ODS10 User Manual

Page 2

Advertising
background image

www.seewaterinc.com or www.oilsmart.org

951.487.8073 • 888.733.9283 • Email:

[email protected]

121 North Dillon Street • San Jacinto, CA 92583

P.O. Box 1269 • San Jacinto, CA 92581

Fail-Safe Technology since 1995.

OIL SMART® SWITCH AND PUMP
INSTALLATION:

CAUTION:

YOU MUST REMOVE ANY

FLOAT SWITCH THAT IS CURRENTLY IN

USE OR SUPPLIED BY PUMP

MANUFACTURER. IF PUMP HAS

MANUAL/AUTO SET, SWITCH TO

MANUAL.
Installation of the Oil Smart® water pump
switch
allows you to comply with State and
Federal regulations while reducing the risk
of adverse publicity, fines and expensive
cleanup costs. The Oil Smart® water
pump switch
prevents inadvertently
pumping oil contaminated waste into the
environment, improves the reliability of your
electric system and provides a safe, dry
work environment for your employees.

FUSING:
Follow the pump manufacturer's
instructions. Do not exceed the Oil Smart®
switch amp rating. A portable devise may
not be attached to a permanent
structure.

THE INITIAL INSTALLATION:
should be in a clean environment, clear of
mud and all metallic debris. The switch
should be installed where the water
intrusion will not directly contact or splash
the switch body.
Mud and other conductive materials left on
the body of the switch will hamper its
operation. Effort must be taken to clean the
switch
prior to leaving initial installation.

CLEAN STRUCTURE:
requires minimum switch maintenance for a
trouble-free operation. Install the switch so
that on and off sensors clear any metallic
material (earth, mud, concrete and all
metals) by a minimum of 2".

SWITCH MAINTENANCE:
The white plastic case must be clean of any
conductive materials (dirt, soap or rust).
Clean with alcohol.

OPERATION:

Normal Condition (Water Only)
The short sensor probe turns the pump "on"
and the long sensor probe turns the pump
"off". When the short sensor is in contact
with water, the pump will continue to cycle
"on and off" until the short sensor detects
oil.

Oil Present Condition
The pump will not cycle if oil is in contact
with the short sensor.

High Water (Oil Present Condition)
If additional water enters the basin, it will
cause the oil layer to rise above the short
sensor, resulting in the pump cycling.

OIL SMART

®

WATER PUMP SWITCH

WATER

WATER

OIL

LAYER

WATER

OIL

LAYER

WIRING DIAGRAM

PUMP

OIL

SMART®

SWITCH

AC

VOLTAGE

SOURCE

BROWN

BLACK

WHITE

FUSE

Printed in U.S.A.

"OFF"

"ON"