Caleffi 6000 User Manual

Page 43

Advertising
background image

18

Installation

Before installing the Caleffi mixing valve, the pipes must be flushed to prevent impurities in the water from affecting performance.

We recommend always installing strainers of sufficient capacity at the inlet from the water main.

Caleffi electronic mixing valves must be installed as shown on the installation diagrams in this manual, taking account of the applicable current

regulations.

Caleffi electronic mixing valve may be installed

either vertically or horizontally, but the actuator must

not be upside down.

The following are indicated on the body of the mixing valve:

-Hot water inlet with red arrow

-Cold water inlet with blue arrow

Check valves

In systems with mixing valves, check valves should be fitted to prevent undesired backflows, as shown in the diagrams.

Commissioning

Due to the special purposes for which the electronic mixing valve will be used, it must be commissioned in accordance with current regulations

and by qualified personnel using suitable measuring instruments. Check that the hot and cold water supply pressures are within the operating

limits of the mixing valve. Check the temperature of the hot water from the storage, T

≥ 60°C.

In the installation log book, record all the parameter settings made and the measurements taken.

Thermal disinfection

The temperatures and corresponding disinfection times for the water system must be chosen according to the type of system and purpose for

which it will be used. Considering the related most advanced legislation, we can take the following criteria as an approximate guide:

T = 70°C for 10 minutes

T = 65°C for 15 minutes

T = 60°C for 30 minutes

Thermal disinfection is usually performed at times when the system is used least, for example at night; this is to minimize the risk of scalding

for users. We recommend carrying out a thermal disinfection every day and at least once a week.

To ensure that thermal disinfection is actually performed at the desired temperature and for the specified time, please refer to the
sections on regulator functions and management of the special programs.

Guide table for thermal disinfection programs

C

0

20

80

60

40

C

0

20

80

60

40

C

0

20

80

60

40

Type of check

Progr.

Use of return

probe

Adjustment

temperature

Disinfection temperature

Adjustment and simple disinfection without

check

0

NO

Flow 50–55°C

Flow: 60°C

Adjustment and disinfection check on flow

temperature

1A

NO

Flow 50–55°C

Flow: 60°C

Adjustment and disinfection check on return

temperature to the central heating system

1B

YES

Flow 50–55°C

Return: 57°C

Continuous disinfection

0 - 1A

1B - 2

Reading only

Flow 55°C - 24 h

See T adjustment

Adjustment and disinfection check with flow

temperature change according to return

temperature

2

YES

Flow 50–55°C

Return: 55°C with adjustment of flow

up to maximum value

Advertising