Caleffi 269 User Manual

Page 3

Advertising
background image

3

Technical specifications

Materials
Shut-off valves
Body:

brass EN 12165 CW617N

Check valve:

brass EN 12164 CW614N

Temperature gauge:

steel / aluminium

Air separator device
Body:

brass EN 12165 CW617N

Instrument holder
Body:

brass EN 12165 CW617N

Seals:

EPDM

O-Rings:

EPDM

Flow meter
Body:

brass EN 12165 CW617N

Transparent level gauge:

PSU

Flow indicator:

brass EN 12164 CW614N

Hydraulic seals:

EPDM

Insulation
Material:

EPP

Average thickness:

30 mm

Density:

45 kg/m

3

Working temperature range:

-5–120°C

Thermal conductivity:

0,037 W/(m·K) at 10°C

Reaction to fire (UL 94):

class HBF

Performance
Medium:

water, glycol solutions

Max. percentage of glycol:

50%

Max. working temperature:

- deaerator side flow:

160°C

- pump side return:

110°C

Max. working pressure:

10 bar

Safety relief valve working temperature range:

-30–160°C

Safety relief valve setting: 6 bar (for other settings, see 253 series)

Check valve min. opening pressure (

∆p): 2 kPa (200 mm w.g.)

Working temperature range of shut-off and check valve:

-30–160°C

Working temperature range of flow meter :

-10–110°C

Flow rate adjustment:

1–13 l/min

Flow rate indicator accuracy:

±10%

Pressure gauge scale:

0–10 bar

Temperature gauge scale:

0-160°C

Connections:

3/4” F

Hose connection:

3/4” M

Fill/drain connections:

with Ø 15 mm hose connection

Grundfos Solar 15-65 pump
Body:

cast iron GG 15/20

Electric supply:

230 V - 50 Hz

Max. pressure:

10 bar

Max. temperature:

110°C

Protection class:

IP 42

Digital regulator
Electric supply:

230 V - 50 Hz

Nominal power consumption:

1,5 VA (12 V (ac))

4 Pt1000 probe inputs

2 relay outputs with semiconductor with contact rating:

1 A

2 temperature probes with working range:

-50–200°C

Probe cable working temperature range:

-50–70°C

2 temperature probes with working range:

-50–200°C

Probe cable working temperature range:

-50–180°C

Ambient temperature range:

0–40°C

Protection class:

IP 20

Dimensions:

172 x 111 x 49 mm

Head available at the circulation unit connections

0

0

H (mm w.g.)

G (m

3

/h)

H (kPa)

0

1

2

3

UPS 15-65

6

5

4

3

2

1

60

50

40

30

20

10

0,2

0,4

0,6

0,8

1,0

1,2

1,4

0

0

H (mm w.g.)

G (m

3

/h)

H (kPa)

0

1

2

3

UPS 15-65

6

5

4

3

2

1

60

50

40

30

20

10

0,2

0,4

0,6

0,8

1,0

1,2

1,4

Power consumption

0

P (W)

G (m

3

/h)

20

30

40

50

60

70

80

0,2

0,4

0,6

0,8

1,0

1,2

1,4

1

2

3

UPS 15-65

268 series

Flow rate adjustment range 1

13 l/min

269 series

Flow rate adjustment range 1

13 l/min

Advertising
This manual is related to the following products:

268