Dwyer MPC User Manual

Page 22

Advertising
background image

Hi

High Alarm Only.

A1Hi

appears in the Secondary Menu.

HiLo

High and Low Alarms. Both

A1Lo

and

A1Hi

appear in the Secondary

Menu, and share the same Alarm 1 Relay output.

SF

Seal Failure ONLY will trigger Alarm.

0t

Over Temperature Failure ONLY will trigger Alarm

SF0t

Both Seal Failure and Over Temperature Failure will trigger Alarm.

With the Alarm Function settings on

0FF

,

SF

,

0t

,

SF0t

certain alarm related menu items

will disappear as those menu items do not apply.

A1t

Alarm 1 Type: Select

AbS

or

dE

. Factory default is

AbS

.

AbS

Absolute Alarm that may be set anywhere within the values of

SCAL

and

SCAH

and is independent of

SP1H

.

dE

Deviation Alarm that may be set as an offset from

SP1H

. As

SP1H

is

changed the Alarm Point will track with

SP1H

.

A1rE

Alarm 1 Reset: Select

0n0F

or

HoLd

. Factory default is

0n0F

.

0n0F

Automatic Reset.

HoLd

Manual Reset. Reset (acknowledge) by simultaneously pressing the

INDEX & DOWN ARROW keys for 5 seconds.

A1Pi

Alarm 1 Power Interrupt: Select

0n

or

0FF

. Factory default is

0FF

.

0n

Alarm Power Interrupt is

0n

.

0FF

Alarm Power Interrupt is

0FF

.

A1iH

Alarm 1 Inhibit: Select

0n

or

0FF

. Factory default is

0FF

.

0n

Alarm Inhibit is

0n

. Alarm action is suspended until the process

value first enters a non-alarm condition.

0FF

Alarm Inhibit is

0FF

.

A1St

Alarm 1 Output State: Select

CL0S

or

0PEn

. Factory default is

CL0S

.

CL0S

Closes Contacts at Alarm Set Point.

0PEn

Opens Contacts at Alarm Set Point.

A1LP

Alarm 1 Lamp: Select

0 on

or

0oFF

. Factory default is

0 on

.

0 on

Alarm Lamp is ON when alarm contact is closed.

0oFF

Alarm Lamp is OFF when alarm contact is closed.

A1td

Alarm 1 Time Delay: Select

0FF

or

1 to 8000

seconds. Factory default is

0FF

.

0FF

Alarm function will operate when triggered at programmed Alarm

Set Point.

1-8000

Alarm function will only operate once the programmed time has

elapsed after the alarm was triggered by the Alarm Set Point.

21

AL2

With
will d

A2t

A2rE

A2Pi

A2iH

A2St

A2LP

A2td

L-20:L-20 2/24/11 10:00 AM Page 21