PROGRAMMING CHART
Use the charts on this and the next page to record the values in your application. You may
want to photocopy the pages if you plan to make programming changes.

Menu

Item

Default

Set At

Description

Primary

PV SP1H

XXXX

Home Position, Process Variable &

SP1H's Value displayed

Menu

Item

Default

Set At

Description

SP1H 23.1

Set Point 1 value (default is in feet)

SP1L 0.0

Set Point 1 off value (default is in feet)

SP2H 23.1

Set Point 2 value (default is in feet)

SP2L 0.0

Set Point 2 off value (default is in feet)

A1Hi 23.1

Alarm 1 (high) value (default is in feet)

A2Lo 2.0

Alarm 2 (low) value (default is in feet)

SFS1

120

Pump 1 Seal Failure Set Point

Secondary

SFS2

120

Pump 2 Seal Failure Set Point

P1rn

XXXX

Total ON Time for Pump 1 in HOURS

since last reset

P2rn

XXXX

Total ON Time for Pump 2 in HOURS

since last reset

P1SF

----

Pump 1 Reset for Seal Failure (---- or FAIL)

P2SF

----

Pump 2 Reset for Seal Failure (---- or FAIL)

P1OT

----

Pump 1 Reset for Over Temperature

(---- or FAIL)

P2OT

----

Pump 2 Reset for Over Temperature

(---- or FAIL)

Menu

Item

Default

Set At

Description

SECr

4

Security Selection

SCAH

23.1

Scale High value (default is in feet)

SCAL

0.0

Scale Low value (default is in feet)

dPt

0.0

Decimal Point Positioning

S1St

POut

Set Point 1 State (selectable POut

(Pumping Out) or PIn (Pumping In))

Secure

S2St

POut

Set Point 2 State (selectable POut

(Pumping Out), PIn (Pumping In), or off)

LdLg

On

Lead/Lag (selectable on or off)

InPC

0.0

Input Correction

OSUP

On

Zero Suppression (selectable on or off)

InP

Curr

Input (selectable current or voltage)

POT

AUtO

Pump Over Temperature controller action

(selectable automatic or manual reset)

26