Adjustment of User Characteristics (USER SET)
1. Push <ENTER> at VALVE mode and ACT RA or ACT DA is

displayed.

2. Push <DOWN> twice, then USER SET mode is started.
3. Push <ENTER>. *P0 SET mode is displayed. In this mode, users

can adjust the first point of characteristic in 16 points. The number
on the LCD is the valve stroke percentage set to P0.

4. Adjust valve stroke percentage using <UP> or <DOWN>.
5. Save it with <ENTER>. While P0 value is being saved, *P1 SET

mode is displayed.

6. *P1 SET mode is used to adjust the second point of characteristic in

16 points. Adjustment method is the same as *P0 SET mode.

7. Save the valve stroke percentage from P2 to P15 in the same way.
8. After adjustment of valve stroke percentage at *P15 SET mode, save

it with <ENTER>.

9. +SER SET is displayed. Sixteen points of valve stroke percentage

are all set. Push <ESC> three times to return to RUN mode.

Adjustment of Tight Shut Open (TSHUT OP)
1.

Push <ENTER> at VALVE mode and ACT RA or ACT DA is
displayed. Push <DOWN> three times at this mode. TSHUT OP is
displayed.

2.

Push <ENTER>. *SHUT OP mode is displayed and in this mode
users can set stroke at the time of Tight Open. Initial setting is done
as 100%, which means cancellation of this function. Adjust the
value (ex: 95.0%) by pushing <UP> or <DOWN> and save it with
<ENTER>. +SHUT OP is displayed.

3.

Push <ESC> three times to return to RUN mode.

Adjustment of Tight Shut Close (TSHUT CL)
1. Push <ENTER> at VALVE mode and ACT RA or ACT DA is

displayed. Push <DOWN> four times at this mode. TSHUT CL is
displayed.

2. Push <ENTER>. *SHUT CL mode is displayed and in this mode

users can set stroke at the time of Tight Close. Initial setting is done
as 0.3%. 0% means cancellation of this function. Adjust the value
(ex: 0.5%) by pushing <UP> or <DOWN> and save it by pushing
<ENTER>. +SHUT CL is displayed.

3. Push <ESC> three times to return to RUN mode.

Adjustment of Split Range (SPLIT)
1.

Push <ENTER> at VALVE mode and ACT RA or ACT DA is
displayed.

2.

Push <DOWN> five times and SPLIT mode is displayed. The
numbers on the LCD are the range of current signal input to the
positioner. 4 to 20 mA current signal is set as the standard.

3.

Push <ENTER>. *SPLIT mode is displayed and input signal range
can be adjusted. Adjust input signal range with <UP> or <DOWN>
and save it with <ENTER>.

4.

+SPLIT mode is displayed while saving adjusted range. Push
<ESC> three times to return to RUN mode.

VIEW Mode
This mode provides users with various information about the Series v275
positioners. In this mode, users can change the valve stroke types
displayed on LCD to % or numbers. Refer to the next table for
information and description displayed on VIEW mode.

1.

Push <DOWN> at AUTO CAL mode and VIEW mode is displayed.

2.

Push <ENTER> at VIEW mode, then information mode is started.

3.

Check information by using <UP> or <DOWN> and push <ESC>.

4.

Push <ESC> again to return to RUN mode.

page 9

(1) Push <ENTER>.

(2) Push <DOWN> twice.

(3) Push <ENTER>.

(4) Adjust with <UP>,

<DOWN>.

(5) Push <ENTER>.

(6) Set P1.

(7) Set P2-P15.

(8) Push <ENTER>.

(9) Push <ESC>

three times.

RUN MODE.

(1) Push <DOWN>

three times.

(2) Push <ENTER>.

(3) Push <ENTER>

after adjustment with

<UP>, <DOWN>.

(4) Push <ESC>

three times.

RUN MODE.

(1) Push <DOWN>

four times.

(2) Push <ENTER>.

(3) Push <ENTER>

after adjustment with

<UP>, <DOWN>.

(4) Push <ESC>

three times.

RUN MODE.

(1) Push <ENTER>.

(2) Push <DOWN>

five times.

(3) Push <ENTER>.

(4) Push <ENTER>

after adjustment with

<UP>, <DOWN>.

(5) Push <ESC>

three times.

RUN MODE.

(1) Push <DOWN>

four times.

(2) Push <ENTER>.

(3) Check data with

<UP>, <DOWN>.

(4) Push <ESC>.

RUN MODE.