The 16mm, Ig04 default settings, Bacnet/ip – Innotech IG04 BACnet Gateway User Manual

Page 5

Advertising
background image

Installation Instructions for Innotech IG04 BACnet Gateway and Vaisala Transmitter / Sensor

Page 5

© Mass Electronics Pty Ltd 2011

Edition 5.0 dated 11/11/2013

Wiring Using The 8-Pin M12 Connector With Independent Cabling For Heating

The wiring example provided below at Figure 1 is recommended for most installations, providing a

separate cabling run of high quality cable for the Vaisala device heating current (if required). The pin

connections for the 8-Pin M12 and wire colours are listed in Table 1 on

page 7

.

For installations that do require the optional heating accessory, ensure a high capacity cable

between the DC Power supply and the Vaisala device is used.

Figure 1:  Wiring guide for Vaisala device M12 Connector with independent cabling for heating

The 8-Pin M12 connector is located on the bottom of the Vaisala device.

NOTE

The 16mm

2

Copper Cable to Earth Ground cable is a critical component for the correct operation of the surge protector.

Ensure this is installed correctly.

NOTE

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Ethernet

&

BACIP

+

-

SHLD

IG04 Default Settings

IP Address: 192.168.2.100 (Static)

S/M: 255.255.255.0

Innotech Port: 20000

BACnet/IP

BACnet Port: 47808

BACnet Instance: 1509

Baud Rate: 19200

Fault Timeout: 30 Sec

-

+

Isolated DC

Power Supply

Earth Ground

Ethernet

Port &

BACnet/

IP Output

SHLD

EOL

C+

C-

SER Terminal Not Used

(Service Tool Connection)

*

1

Wire WXT520 / WMT52 Device to the

WSP150 Surge Protector in accordance with

appropriate Vaisala technical documentation.

Innotech IG04

BACnet Gateway

BL

K

W

ire

(V

in

−)

R

ED

W

ire

(V

in

+)

24V

0V

Shielded cable length should NOT exceed

3m when connecting WXT520 / WMT52

Device to WSP150 Surge Protector

If a surge protector is not installed, connect the cables directly

RS485 [+]

S

RS485 [-]

RS485 [

Shield

]

RS485 Line

Termination

Jumper

+

-

BLU Wire (RX−)

GRY Wire (RX+)

1

2

3

4

5

6

7

8

YE

L

(V

h+

)

PN

K

(V

h−

)

R

ED

W

ire

(V

in

−)

BR

N

W

ire

(V

in

+)

*

1

R

ED

W

ire

(V

h+

)

BL

K

W

ire

(V

h−

)

24V to 32V DC

@ < 200mA

*

2

@ < 800mA

*

3

*

2

When heating is NOT used.

*

3

Higher heating currents cause

voltage drop. Select cable with sufficient

cross section for longer runs.

Note: Colour coded as per

Vaisala documentation

G

R

Y

W

ire

(R

X+

)

BL

U

W

ire

(R

X−

)

Vaisala WXT520 Weather Transmitter / WMT52 Ultrasonic Wind Sensor

M12 connector pin-out

*

1

WSP150 Surge Protector

*

1

16mm² Copper Cable

HTTP Port: 80

SER

WXT

MSTP

IG04 Default Settings

IP Address

192.168.2.100 (Static)

Subnet Mask

255.255.255.0

HTTP Port

80

Innotech Port

20000

BACnet/IP

BACnet Port

47808

BACnet Instance

1509

Baud Rate

19200

Fault Timeout

30 seconds

Advertising