Noby-65 Installation Manual & Operating Instructions (Rev.1)

Page 2 of 12

FIRST POWER-UP

We strongly recommend that the Noby-65 is first powered up with all 10K End Of Line resistors fitted at the panel,
as supplied by the factory. In this way you can gain confidence that the panel is operating correctly before
introducing detector and sounder circuits.

Power-Up With Battery

• Turn the Keyswitch to the OFF position.
• Connect the black battery lead to the battery –‘ve terminal.
• Connect the red battery lead to the battery +’ve terminal. It is normal to see a small spark.
• 60s Start-up Period: i) All LEDs flash for 60s *.

ii) The Buzzer output will make a pulsing sound (if connected).

After Start-up:

i) The green Power LED flashes.

ii) The yellow Fault/Alarm LED is lit.

iii) The red Sabotage LED is lit (because Noby-65 lid is removed).

* The 60s Start-up Period can be prematurely terminated by turning the Keyswitch to FULL for 4s,

and then back to OFF.

• Perform a System Reset: Momentarily turn the Keyswitch to FULL and then to OFF within 2s.

Observe a 2s LED test.

• After System Reset: i) The green Power LED is off (because the 230VAC is absent).

ii) The yellow Fault/Alarm LED is lit.

iii) The red Sabotage LED is lit (because Noby-65 lid is removed).

• Connect 230VAC supply to the 230v/50Hz AC screw terminal block.
• Replace the Noby-65 panel lid: observe the yellow Fault/Alarm LED turn off.
• Switch on the 230VAC power and observe the green Power LED flash (indicating 230VAC restored).
• Perform a System Reset: momentarily turn the Keyswitch to FULL and then to OFF within 2s.

Observe a 2s LED test.

• The panel should now be in a quiescent standby state with only the green Power LED lit.

Power-Up With 230VAC

• Turn the Keyswitch to the OFF position.
• Connect a 230VAC power supply to the 230v/50Hz AC screw terminal block, and switch on.
• 60s Start-up Period: i) All LEDs flash for 60s *.

ii) The Buzzer output will make a pulsing sound (if connected).

After Start-up:

i) The green Power LED will flash.

ii) The yellow Fault/Alarm LED will be lit.

iii) The red Sabotage LED is lit (because Noby-65 lid is removed).

* The 60s Start-up Period can be prematurely terminated by turning the Keyswitch to FULL for 4s,

and then back to OFF.

• Perform a System Reset: Momentarily turn the Keyswitch to FULL and then to OFF within 2s.

Observe a 2 second LED test.

• After System Reset: i) The green Power LED is lit (230VAC OK indication).

ii) The yellow Fault/Alarm LED is lit.

iii) The red Sabotage LED is lit (because Noby-65 lid is removed).

• Connect the black battery lead to the battery –‘ve terminal.
• Connect the red battery lead to the battery +’ve terminal. It is normal to see a small spark.
• Replace the Noby-65 panel lid: observe the yellow Fault/Alarm LED turn off.
• Perform a System Reset: momentarily turn the Keyswitch to FULL and then to OFF within 2s.

Observe a 2s LED test.

• The panel should now be in a quiescent standby state with only the green Power LED lit.



IMPORTANT: TAKE CARE TO CONNECT THE BATTERY CORRECTLY.
Whilst there is a measure of protection against accidental reverse connection of the battery, such action will almost
certainly blow fuse F3, and may cause permanent damage to the Noby-65 panel. Such damage is identifiable to
Noby UK Ltd. and is not covered by the warranty.