Setra Systems Model 3100/3200

Pressure Transducer

1.0 GENERAL INFORMATION

Every Model 3100/3200 has been tested and calibrated before shipment.

Setra Systems 3100/3200 pressure transducers sense gauge pressure and con-

vert this pressure difference to a proportional high level analog output. The

following standard output and excitation versions are offered:

ExcITATION

OuTPuT

10 to 30 VDc

4 to 20 mA

5 VDc ±10%

0.5 to 4.5 Ratiometric

0 to 10 VDc

0.5 to 4.5 VDc

2V above Full Scale to 30 VDc max @ 4.5mA

0 to 5 VDc

1 to 6 VDc

1 to 5 VDc

2mV/V (nominal)

2.0 MEcHANIcAL INSTALLATION

2.1 Media compatibility

Model 3100/3200 transducers are designed to be used with any gases or liquids

compatible with 17-4 PH Stainless Steel.

2.2 Environment

The operating temperature limits of the 3100/3200 are -40°F to +250°F

(-40°c to +125°c). The compensated temperature range is -40°F to +250°F

(-40°c to +125°c).

Ingress Protection: all transducers/transmitters have a minimum IP rating

of IP65 in accordance with BS EN 60529.

2.2 Electrical (See Diagram A, page 2 for electrical connections)

cable connectors: where client cable are used, the cable shield must be

terminated by the client. The shield should not be connected to the

transducer body.

Setra uses a 4-core color coded cable enclosed by a braided shield

terminated within the transducer housing. conformance of requirement

with relation to the cE Mark, is only valid with Setra’s approved cable.

Frequency Response: <1ms for conditioned Outputs.

Maximum current Draw: 2-wire Transmitter = 20mA, Transducer in

voltage mode = 8mA, transducer in millivolt mode = 3.5mA

EMc Data: Meets the requirements of cE.

This product complies with EN61326-1 and EN61326-2-3 Electrical Equipment

for Measurement, control and Laboratory use – EMc Requirements for Mini-

mum Requirements and Industrial Locations. Special caution should be taken to

meet Standard EN61000-4-5. Surge Immunity if any of the following conditions

apply to