3200

Series

18 ACS 3216 Operators Manual

S A F E

SAFE OUTPUT POWER

To set the output level in a sensor break (open
circuit) condition

-100.0 to 100.0% limited by OP.HI and OP.LO

0.0%

L3

none

Transfer between Auto/Manual/Auto is
bumpless

SteP

Transfer from Auto to Manual, the output
goes to a pre-set value (F.OP)

F . M O D

FORCED MANUAL OUTPUT MODE

Selects how the loop behaves on transfer from
Auto to Manual.

Transfer from Manual to Auto is always
bumpless.

Last

Transfer from Auto to Manual, the output
goes to the previously set manual value

none

L3

Lin

Linear

OIL

Oil cooling

H20

Water cooling

C o o l . t

NON-LINEAR COOLING TYPE

This selects an algorithm most suited to the
type of cooling. Typically used in extruders.

Fan

Forced air cooling

As order
code

Conf

F . O P

FORCED OUTPUT

To pre-set a value for the Manual output
when F.MOD = STEP

-100.0 to 100.0% limited by OP.HI and OP.LO

0.0

L3

Auto

To select automatic operation

Man

To select manual operation

A - M

LOOP MODE – AUTO MANUAL OFF

OFF

Control outputs inhibited

L3

No

l b r

LOOP BREAK STATUS

YES

Shows the current status of loop break.

Read only

ALARM LIST

‘ALARM’

Name

Scrolling Display

Parameter Description

Value

Default

Access
Level

none

Alarm not configured

Hi

Full Scale High

Lo

Full Scale Low

d.Hi

Deviation High

d.Lo

Deviation Low

A1.TYP

ALARM 1 TYPE

Selects the type of alarm

bnd

Deviation band

As order
code

Conf

A 1 . - - -

ALARM 1 SETPOINT

Alarm 1 threshold value.

The last three characters show the type of
alarm configured from the above list

Instrument range

0

L3

OFF

Alarm off

A 1 . s t s

ALARM 1 OUTPUT

Indicates the status of the alarm

On

Alarm on

Read

only

A1.HYS

ALARM 1
HYSTERESIS

See description in manufacture manual

0 to 9999

Conf

none

Non-latching

Auto

Latching with automatic
resetting

Man

Latching with manual
resetting

A1.LAT

ALARM 1
LATCHING TYPE

See description in manufacture manual

Evt

Event (no alarm flashing
beacon but messages can
be displayed)

As order
code

Conf

No

No blocking

A1.BLK

ALARM 1
BLOCKING

See description in manufacture manual

yes

Blocking

No

Conf

The above parameters are repeated for Alarm 2, A2; Alarm 3, A3; Alarm 4, A4

TIMER
LIST

‘t i m e r ’’

Name

Scrolling
Display

Parameter Description

Value

Default

Access
Level

none

Timer disabled

dwel

Dwell

deLY

Delayed switch on

SFST

Soft start

T M . C F G

TIMER
CONFIGURAT
ION

Timer type configuration

prog

Programmer

As order
code

L3

Hour

Hours

HH:MM

T M . r e s

TIMER
RESOLUTION

To set the time units

Min

Minutes

MM:SS

Conf

R/O

L3