Troubleshooting

Problem

Cause

Solution

Display does not light up

No Electricity

Check that the power supply cable is correctly
connected to both the chiller and outlet. Check that
the power switch is ON. Check that the fuse is intact.

Dirty Air Filter

Clean Air Filter as described on page 18.

Ambient Temperature

is too high

Lower the ambient temperature to below 95° F/35° C

Obstructed

Ventilation Grate

Remove the obstruction or create a ventilation hole.

Broken Fan

Contact service at [email protected]

UV lamp

Replace the UV lamp with an appropriate TECO UV
replacement, available at www.tecous.com

Water temperature

probe has been

damaged

Contact service at [email protected]

Compressor overload

probe is damaged

Check air filter, check that ventilation fans are running.
Contact service at [email protected]

Temperature displayed
is not correct

Water is losing or

gaining heat through

long and/or un-

insulated tubing

Reduce length of tubing, insulate the tubing.

Check for obstructions in tubing

Check that the pump is working

Water may not be circulating through chiller correctly

Chiller does not come on
until aquarium temperature
is several degrees higher
than set point

Temperature offset is

incorrect

Reset temp differential - see instructions below

Water flow through chiller
has slowed

Calcium Buildup

Disconnect chiller from aquarium. Run a 50% solution
of vinegar and water through chiller for 24 hours to
dissolve buildup. Thoroughly flush chiller with Ro/DI
before connecting to aquarium.

Press and hold “SET” for 10 seconds.

1

The display will show a value of 1 to 20 - this is the current set differential

Use the arrow Keys to change the set differential

2

The set differential reflects the number of degrees variance upward

from the set temperature you wish to allow. For example, if you have the
set temperature at 77° F, but do not want the chiller to turn on until it
reaches 80° F, set the differential value to 3. The default setting allows

a variance of 1.5° F from the set temperature before the chiller turns on.

This value is intended to protect the compressor from excessive wear, we

recommend a minimum of 1.5 set differential.

Changing UV Bulb

Turn off chiller and unplug the chiller, Remove the housing

1

(see directions on p.18)

Unscrew the ring nut for the UV sterilizer port.

2

Remove rubber stopper from the quartz sleeve

3

Unplug the old UV lamp from the 4-pin socket., remove and discard lamp.

4

Slide new UV lamp into quartz sleeve, plug into 4-pin socket, return rubber stopper into sleeve

5

Do not touch the glass of the UV bulb with your bare hands.

Tighten ring nut over quartz sleeve

6

Replace housing and screws

7

Open shut off valves, restart pump and check for leaks. Turn UV on by pressing UV button.

8

Hold down UV button for 10 seconds to reset AL2 code.

9

TR

30

TR

60

It is time to replace the UV Lamp
when the AL2 code flashes on the
control panel

Do not touch the glass of the UV bulb with your bare hands.
Oils on your hands will dramatically decrease the lifespan of the UV lamp. Use a clean
cloth to handle the lamp during installation.