TOHO ELECTRONICS TTM-10L User Manual

Page 3

Advertising
background image

5.3 OTHER DISPLAY INDICATIONS

Shown whenever Input value exceeds the High limit of Display range, or the snapping of the Input line.

:

Shown whenever Input value exceeds the Low limit of Display range, or the snapping of the Input line at 4-20mA.

:

Shown for Memory error. Please contact us for repairing service.

:

Shown for A/D converter error. Please contact us for repairing service.

:

Shown for Auto-tuning error,Push any keys for resetting this display.

:

Shown when Parameter being changed during Key lock.

:

Shown during Auto-tuning.

:

5.4

INFORMATIONS FOR EACH PARAMETER

・MODE Display

Character

Display conditions &

Descriptions

Initial Value

Indications

Remarks

Process

Normal Display after the

ariable

Input of Power

V

()∼

Shown on PID or

Setting range:SV Limiter Low

SV Limiter High

()

ON/OFF control.

Setting

:1℃(゚F)

Value

Setting unit :Thermocouple

:1/0.1℃(゚F)

R.T.D.

:1/0.1/0.01

Current

Setting range

Thermocouple

Shown when Alarm

:-1999∼9999

Alarm

R.T.D.

Output s installed and

:-199∼999/-199.9∼999.9

i

Output

Current

set at Low Limit Alarm

:-1999∼9999/-199.9∼999.9/

Setting

Output or High/Low Limit

-19.99∼99.99

Low Limit

Setting unit

Alarm Output.

:Same as that of B.Setting Value.

Setting range

Shown when Alarm

:Same as that of C.Alarm Output

Alarm

Output s installed and

Setting Low Limit.

i

Output

Setting unit

set at High Limit Alarm

:Same as that of B.Setting Value.

Setting

Output or High/Low Limit

High Limit

Alarm Output.

Press UP/DOWN key more than 2 seconds for start/reset

Shown on PI

control.

D

AT start

of Auto-tuning,(AT)

:

.



display

Shown during AT

:





Shown without AT.

Shown alternatively during A T.

NORMAL

&

:



PARAMETER DISPLAY

Propor-

Setting range

Setting unit

Shown on

control.

:0.1∼200.0

:0.1%



PID

tional Band

Integral

Setting range

Setting unit

second

Shown on

control.

:0∼3600

:1

PID

Time

Integral operation

at

OFF

=0

Deriva-

Setting range

Setting unit

second

Shown on

control.

:0∼3600

:1

PID

tive Time

Derivative operation OFF

=0

at

Output

Setting range

Setting unit

second

Shown on

control.

:1∼120

:1

PID



Proportional
Cycle

Setting range

Thermocouple

Shown on ON/OFF

:0∼9999

Output

R.T.D.

control.

:0∼999/0.0∼999.9

:0∼9999/0.0∼999.9/

Sensitivity

Current

0.00∼99.99

.

..

.

Setting unit

:Same as that of above B.Setting Value

Setting range

Same as that of above

Displays at ON/OFF

C.Alarm Output

control.

OFF point

Setting Low Limit.

B.Setting Value.

position

Setting unit

Same as that of above

The Kind of Output needs

**※

Kinds of

to be selected"

"or"

"

**

Input Type

**

Input Type





Pt100

before purchase.

INPUT/

K thermocouple

therm-

J thermocouple

ocouple

OUTPUT





JPt100

E thermocouple

he following Input types

4-20mA DC

INPUT

T





T thermocouple

are NOT selective.





Output Type



R thermocouple

4-20mDC

←→



S thermocouple

Relay contact output

thermocouple

INPUT

4-20mADC



N thermocouple

SSR Drive Output

W5Re/W26Re

R.T.D←→4-20mADC



