TOHO ELECTRONICS TTM-10L User Manual

Page 7

Advertising
background image

ORDERING INFORMATION

8.

TTM−10L−□−□−A□

記号

記号

記号

Input

Output

Option

Communication

M1

Thermocouple / R.T.D.

None

4 ∼

20mA DC

RS−485

Relay contact

Communication

M2

SSR drive volt.

RS−232C

SPECIFICATIONS

9.

9.1 GENERAL SPECIFICATION(COMMON)

Power Supply Voltage

12VDC±10%

or

24VDC±10%

Power Consumption

12VDC:below 1.4W

24VDC:below 2.7W

Operation

Temperature

0∼50℃

35∼85%RH (Avoid making dew)

environment

& Humidity
range
Supply

12VDC±10%

or

24VDC±10%

Voltage

Transportation

Temperature

−20∼60℃

35∼85%RH (Avoid making dew)

storage

& Humidity

environment

range

Drop from the

Vibration

0.5G

Impact

0∼50G

Package

Condition

Condition

Drop test

60cm

height

Mechanical

Weight

TTM-10L less then 80g

Specifications

9.2 GENERAL SPECIFICATION(DETAILS)

Switchable.

K、J、E、T、N、R、S、W5Re/W26Re

Thermocouple

Input resistance: more than 1MΩ
Bias Current:Approx 0.2μV/Ω
Burn out:"OVER"(

)



Switchable.

PV INPUT

Kind of

Pt100/JPt100

INPUT

R.T.D.

External resistance:

5Ω(Per wire)

less than

Burn out:Shown"OVER"(

)



same display shown at snapping of either A,B or b.

CURRENT

Input resistance:250Ω

(4-20mA DC)

Burn out:Shown"UNDER"(

)



Sampling
cycle

0.5sec(same as Output alteration cycle)

PV Display

4figures

7segmentLCD

Letter height 7mm

Character Display

1figure

7segmentLCD

Letter height 5mm

PV/Character

Control Output

OUT Lamp

Light ON at Control Output

Display

Alarm Output

AL Lamp

Light ON at Alarm Output

Communication

COM Lamp

Light ON at operating Communication

Thermocouple

±0.5%+1digit of indicated value,or±4℃(8),

i on of

Stipulated by the standard environment and the convers

Indication

indicated value)

Accuracy

R.T.D.

±0.5%+1digit of indicated value, or±1.2℃(2.4),

i on of

Stipulated by the standard environment and the convers

indicated value)

±0.5%+1digit of Setting Value Limiter Span.

CURRENT (4-20mA DC)

i on of

Stipulated by the standard environment and the convers

indicated value)

All Output functions being OFF for approximately 4 seconds after Power ON.

Output at

Control Output being OFF at abnormal Process Value.

Special cases

Contact specification :1a Contact point.
Contact capacity :250VAC 3A(Load resistance)

Control &

Relay Contact

Output

Kind of

Output

Endurance :more than 100,000 times.

Section

Output and

SSR Drive

Output Voltage :OFF time;0V

ON time ;12V+10% -20%

Rating

Voltage Output

Loaded resistance :0ver 600 Ω

Alarm

Contact specification :1a Contact point.
Contact capacity :250VAC 0.5A(Load resistance)or 125VAC 1A(Load resistance)

Functions

Alarm Output

Endurance :more than 100,000 times.

Advertising