Before using this meter, read all safety information carefully. In this manual the word “WARNING” is used to indicate

conditions or actions that may pose physical hazards to the user. The word “CAUTION” is used to indicate conditions or

actions that may damage this instrument.

WARNING!

This analyzer extracts combustion gases that may be toxic in relatively low concentrations. These gases are exhausted

from the back of the instrument. This instrument must only be used in well-ventilated locations.It must only be used by

trained and competent persons after due consideration of all the potential hazards.

P

reflight

C

heCkliSt

• Clean particle filter

• Water trap and probe line are empty of water

• Power on and zero

• All hose and thermocouple connections are properly secured

• Flue gas probe is sampling ambient FRESH air

• Water trap is fitted correctly to the instrument

• Flue temperature plug is connected

• Inlet temperature probe is connected if required

S

ettiNg

i

Nlet

t

emPerature

To correctly calculate net temperature and combustion efficiency it is important to have the correct inlet tempera-

ture set. Two methods are available to properly establish the inlet temperature

• Non-ducted systems. If the SmartBell is being used on a system that uses combustion air from the space near the

appliance simply turn the analyzer on without the flue probe connected. The SmartBell will use an ambient sensor inside

the handset as the inlet temperature to determine net temperature.

• Ducted systems. If the SmartBell is being used on a system that brings in outside air for combustion air it is

important to set the inlet temperature prior to taking flue gas readings. To properly set inlet perform the following steps

during startup of the SmartBell

1. Connect the flue temperature connector only to the SmartBell

2. Place the flue probe in the combustion air inlet stream (you will need to drill a _” hole for access)

3. Turn on the SmartBell and allow to complete the zero process.

4. Connect the flue gas connector to the SmartBell and proceed to combustion measurements

• The temperature measured during the zero countdown has now been stored, and will be used to determine

the net temperature.

a

Nalyzer

C

oNNeCtioNS

NOTE:

Take care when inserting the temperature

probes as the pins are polarized. Insert with the smaller pin

into input marked posotive. (+)

WARNING!

Turning the pump off while the probe is in the flue

will leave toxic gases inside the analyzer. Once data

has been read, it is advisable to purge the

unit with fresh air as soon as possible. To do this,

with the probe removed from the flue, turn ON the

pump. Always allow the readings to return to zero

(0.09 for CO2) prior to shutting the unit off.

(continued on pg.2)