What results are generally acceptable 6, Co91 – UEi Test Instruments SMART BELL User Manual

Page 8

Advertising
background image

a

tmoSPheriC

g

aS

f

ired

B

urNerS

• Oxygen .............................................................................6.8 to 7.9% O2

• Stack Temperature ......................................................... 325 to 500°F

• Draft (Water Column Inches) .......................................... -.02 to -.04wc”

• Carbon Monoxide (parts per million) ............................ <100ppm

g

aS

f

ired

P

ower

B

urNerS

• Oxygen ............................................................................. 8.5to 10.2% O2

• Stack Temperature ......................................................... 275 to 500°F

• Stack Draft (Water Column Inches) ............................... -.02 to -.04wc”

• Overfire Draft (Water Column Inches) .......................... -.02wc”

• Carbon Monoxide (parts per million) ............................ <100ppm

o

il

f

ired

B

urNerS

(#2 o

il

f

uel

)

• Oxygen .............................................................................10 to 12% O2

• Stack Temperature ......................................................... 325 to 600°F

• Stack Draft (Water Column Inches) ............................... -.04 to -.06wc”

• Overfire Draft (Water Column Inches) .......................... -.02wc”

• Carbon Monoxide (parts per million) ............................ <100ppm

• Smoke .............................................................................. 0

(or manufacturer’s recommendation)

P

oSitive

o

verfire

g

aS

& o

il

• Oxygen ............................................................................. 7 to 13% O2

• Stack Draft (Water Column Inches) ............................... -.02 to -.04wc”

• Overfire Draft (Water Column Inches) .......................... +0.4 to +0.6wc”

• Carbon Monoxide (parts per million) ............................ <100ppm

NOTE: Follow manufacture guidelines for the specific equipment being serviced.