MEASURING AIR VOLUME CONT.

We recommend the following number of access holes depending on duct

size;

• 18” or less – Two access holes 6” apart

• 18”~30” – Five access holes

• 30”~36” – Six access holes

• Greater than 36” – Seven access holes

ACCESS HOLE SPACING
Use the Log-Tchebycheff Rule for rectangular ducts to determine spacing

for access holes.

Number of access

holes per side

Position relative to inner wall

(multiplier)

5

0.074, 0.288, 0.500, 0.712, 0.926

6

0.061, 0.235, 0.437, 0.563, 0.765, 0.939

7

0.019, 0.153, 0.217, 0.361, 0.639, 0.783,

0.847, 0.923, 0.981

Example – for a 20” inside dimension select 5 access holes.
• Access 1, 20 x 0.074 = 1.48” from wall (use 1 ½“)
• Access 2, 20 x 0.288 = 5.76” from wall (use 5 ¾”)
• Access 3, 20 x 0.500 = 10” from wall (use 10“)
• Access 4, 20 x 0.712 = 14.24” from wall (use 14 ¼“)
• Access 5, 20 x 0.926 = 18.52” from wall (use 18 ½“)

SAMPLE CALCULATED LOCATIONS

Access

Holes

5

Access

Holes

6

Access

Holes

7

Width

24

Width

30

Width

36

0.074

1.8

0.061

1.8

0.053

1.9

0.288

6.9

0.235

7.1

0.203

7.3

0.500

12.0

0.437

13.1

0.366

13.2

0.712

17.1

0.563

16.9

0.500

18.0

0.926

22.2

0.765

23.0

0.634

22.8

0.939

28.2

0.797

28.7

0.947

34.1