Installation and Maintenance

Lamp lead (rubber
sleeved female
receptacle)

Note that lamp connector pin pattern
is NOT square.

It can be mounted from either side
and top or bottom depending on the
orientation of the installed lamp.

Electrical

NOTICE: All 24 volt UV equipment for HVAC systems
(regardless of manufacturer) must be installed using
a separate, dedicated minimum 40VA transformer to
avoid the possibility of voiding UL certification of the
HVAC system.

The screw holes on the UV lamp
need to be parallel to the lamp lead
cord on the back of the female
receptacle for correct assembly!

Lamp screw holes and lamp lead
cord need to be parallel

UVC lamp

Horizontal orientation of
the lamp lead requires
installing the lamp with
screws left to right.

Installation steps for internal mounting of power supply:

1. Mount power supply inside of the air handler but out of the air stream as much as

possible. Place the power supply close to the control panel for ease of connecting to

24 VAC or appropriate voltage according to the power supply label.

2. To utilize the internal mounting bracket, first install the bracket inside the air handler

in a location that will position the UV lamp such that it bathes the entire surface to be

treated. Plug the lamp connector onto the lamp and snap into the bracket.

Note: The rectangular pin pattern can be mated in two positions only.

3. Connect power wires to a dedicated minimum 40VA transformer. This must be done in

accordance with all state and local electrical and building codes.

Maintenance

Never perform maintenance on the UV unit without disconnecting power. Typical

maintenance consists of replacement of the ultraviolet (UV) lamps. UV lamps undergo a

photochemical process during operation, that slowly reduces the amount of UV light

generated to disinfect the air and surfaces. For optimum air stream disinfection UV lamps

should be replaced annually. For surface disinfection, lamp replacement should be

performed no later than every two years (see below, “Important Information about UV

lamp replacements”). When installing new lamps, ensure that the lamp glass is free from

any fingerprints or debris, as this may alter the path of the UV energy. Use rubbing

alcohol and a dry cloth to remove any surface contamination.

Important information about UV lamp replacements

Replace UV lamp(s) annually in order to maintain optimum effectiveness in the reduction

of pathogens such as bacteria, viruses and microscopic mold. Lamps operating after a

period of 18,000 hours (two years) no longer provide adequate UV-C. When the UV lamp(s)

reach the end of the 18,000 hour useful operating life, the unit automatically turns off. The

UV lamp must be replaced and the power supply reset. Do not reset the power supply

without replacing the UV lamp as worn out UV lamps draw excessive electrical

current which may result in damage to the UV system, and may void the warranty.

Important! Read before installation

We recommend that this unit be installed and maintained by a trained HVAC
professional technician.

Installation steps for external mounting of power supply:

1. Determine a suitable location to install unit housing. Mounting location should be of

sufficient strength as to support the unit, otherwise reinforcement of the ductwork may

be necessary. Fasten the unit in place with two self-tapping screws (supplied).

2. Select location for UV lamp module. Drill a 1" hole. Install mounting plate over

drilled hole with screws provided. Insert UV lamp into hole. Attach to mounting plate

system with two self-tapping screws (supplied).

3. Attached the rubber lamp connector fully onto the installed UV lamp assembly. Be

sure the four pinholes are orientated properly to the four matching pins on the lamp

(see diagram at right).

4. Connect power wires to a dedicated minimum 40VA transformer or hardwire to

appropriate voltage based on requirements listed on power supply label.

This should be done in accordance with all state and local electrical and

building codes.

Notes: The UV lamp assembly can be removed independently, by removing the

two screws in the lamp holder.

The rectangular pin pattern allows connection in two positions (see other

side of this sheet).

A UV status viewport lens is supplied to verify lamp operation. Drill a 3/8"

hole within a 3" radius around the lamp, and on the “lamp side” of the “V” in

the light shield. Snap viewport into place.