Faults – Atmos Energy HE26 User Manual

Page 42

Advertising
background image

8.

FAULTS

When the controller detects a fault, the red fault LED flashes (above the
Reset button) and a fault code is shown on the Temperature display.
After the fault has been remedied, the controller can be restarted by

pressing the Reset button for 5 secs.

The following faults are detected and displayed:-

Temperature
display

Description Possible

cause/remedy

10, 11, 12, 13, 14 Sensor fault S1

•

Check the wires for breaks

•

Replace S1

20, 21, 22, 23, 24 Sensor fault S2

•

Check the wires for breaks

•

Replace S2

0

Sensor fault after self-check

•

Replace boiler sensor S1 and/or S2

1

Temperature too high

•

Air in system

•

Pump does not run

•

Too little circulation in system, radiators closed,
pump setting too low

2

Exchange S1 and S2

•

Check the cable loom

•

Replace S1 or S2

4

No flame signal

•

Gas tap closed

•

Incorrect ignition distance

•

Gas inlet pressure too low or disappears

•

Gas valve or ignition unit does not receive voltage

5

No flame signal

•

Condensate discharge blocked

•

Check setting of gas valve

6 Flame

detection

fault

•

Replace ignition cable + spark probe

•

Replace ignition unit

•

Replace controller

8

Fan speed incorrect

•

Fan rubs against casing

•

Wiring between fan and casing

•

Check the wires for poor contact (tacho signal)

•

Replace fan

29, 30

Gas valve relay fault

•

Replace controller


42