Operator interface – American Standard CH530 User Manual

Page 44

Advertising
background image

CDHF-SVU01C-EN

44

Operator
Interface

Chiller
Description

Resolution or (Enumerations), Default

Units

1. Front Panel Control Type

(Chilled Water, Hot Water), Chilled Water

Enum

2. Front Panel Chilled Water Setpt

(3)
+ or – XXX.X

Temperature

3. Front Panel Hot Water Setpt

(3)
+ or – XXX.X

Temperature

4. Front Panel Current Limit Setpt

XXX (4)

Percent RLA

5. Front Panel Base Load Cmd

On/Auto

enum

6. Front Panel Base Load Setpt

XXX

Percent

7. Front Panel Ice Build Cmd

On/Auto

Enum

8. Front Panel Ice Termn Setpt

XXX.X

Temperature

9. Ice to Normal Cool Timer Setpt

(0-10), 5 min

Minutes

10. Differential to Start

XXX.X

Temperature

11. Differential to Stop

XXX.X

Temperature

12. Setpoint Source

*(BAS/Ext/FP, Ext/ Front Panel, Front Panel),

BAS/Ext/FP Default

Enum

*Follows hierarchy of selection from left to right (except for ice building which is “OR” logic).

Feature Settings
Description

Resolution or (Enumerations), Default

Units

1. Chilled Water Reset

(Constant, Outdoor, Return, Disable), Disable

Enum

2. Return Reset Ratio

XXX

Percent

3. Return Start Reset

XXX.X

Temperature

4. Return Maximum Reset

XXX.X

Temperature

5. Outdoor Reset Ratio

XXX

Percent

6. Outdoor Start Reset

XXX.X

Temperature

7. Outdoor Maximum Reset

XXX.X

Temperature

8. Ext Chilled Water Setpoint

(Enable, Disable), Disable

Enum

9. Ext Current Limit Setpoint

(Enable, Disable), Disable

Enum

10. Ice Building Feature Enable

(Enable, Disable), Disable

Enum

11. Ext Base Loading Setpoint

(Enable, Disable), Disable

Enum