Operator interface – American Standard CH530 User Manual

Page 45

Advertising
background image

45

CDHF-SVU01C-EN

Operator
Interface

System Mode Overrides
Description

Resolution or (Enumerations), Default

Units

Monitor Value

1. Compressor

XXX / (Auto,Manual [0-100] ), Auto

Enum

IGV % Open

Control Signal

Evap. LWT
AFD Freq.

2. Evap Water Pump

(Auto, On), Auto

Enum

1) Evap Flow
status
2) Override Tim
e Remaining

3. Cond Water Pump

(Auto, On), Auto

Enum

1) Cond Flow
status
2) Override Time
Remaining

Circuit Mode Overrides
Description

Resolution or (Enumerations), Default

Units

Monitor Value

1. Oil Pump

(Auto, On), Auto

Enum

1) Diff press
2) Override Time
Remaining

2. Clear Restart Inhibit Timer
3. Purge Exhaust Circuit Test

(Off, On), Off

Enum

none

4. Purge Regen Cycle

(Off, On), Off

Enum

Carbon Temp

5. Front Panel Ckt Lockout

(Not Locked Out, Locked Out), Not Locked Out

Enum

Purge
Description

Resolution or (Enumerations), Default

Units

1. Purge Operating Mode

(Auto, On, Adaptive, Stop), Adaptive

Enum

2. Daily Pumpout Limit

XXX

Minutes

3. Disable Daily Pumpout Limit
(0 to disable)

0, XX

Hours

4. Purge Liquid Temp Inhibit

(Enable, Disable), Enable

Enum

5. Purge Liquid Temp Limit

XXX.X

Temperature

Display Settings
Description

Resolution or (Enumerations), Default

Units

1. Date Format

(“mmm dd, yyy”, “dd-mmm-yyyy”), “mmm dd, yyy”

Enum

2. Date
3. Time Format

(12-hour, 24-hour), 12-hour

Enum

4. Time of Day
5. Keypad/Display Lockout

(Enable, Disable), Disable

Enum

6. Display Units

(SI, English), English

Enum

7. Pressure Units

(Gauge, Absolute), Absolute

Enum

8. Language

(English, Selection 2, Selection 3), English (2)

Enum

(1) Temperatures will be adjustable to 0.1 degree F or C. The Main Processor provides the minimum and maximum allowable value.
(2) Adjustable to the nearest whole number percent. The Main Processor provides the minimum and maximum allowable value.
(3) Terminates with 10 minutes if inactivity
(4) The Date and Time setup screen formats deviate slightly from the standard screens defined above. See the time and date section for further details.
(5) Enables a DynaView

Lockout screen. All other screens timeout in 30 minutes to this screen when enabled. The DynaView

Lockout Screen displays a 0-9 keypad to

permit the user to exit the lockout with a fixed password (1-5-9 + Enter). See lockout setion for further details.

(6) Language choices are dependent on what has been setup in the Main Processor. Language selections will include English and qty 2 alternate as loaded by TechView

.

Language shall always be the last setting listed on the Display Settings menu. This will allow a user to find language selection if looking at an unrecognizable language.

(7) Manual Compressor Control allows an operator to override the Auto Control and manually control the compressor while in operation. This is not active during Stop

mode.