ADCP-80-412

N Issue 1 N April 2000

Page 4
© 2000, ADC Telecommunications, Inc.

BLANK PANEL (FRONT)

CABLE TROUGH (REAR)

FUSE PANEL

RESERVED FOR

MISCELLANEOUS

APPLICATIONS

RESERVED FOR

MISCELLANEOUS

APPLICATIONS

DSX

PANEL

DSX

PANEL

14093-A

FILLER

PANEL

FILLER

PANEL

NOTE: SENSOR AND POWER ATTACHMENT POSITION AND
APPEARANCE SHOWN EXAGGERATED FOR CLARITY.

Figure 1. Bay Tracer Cable Routing

1. Attach the Bay Tracer Electronic Sensor Device mounting bracket to the top cross

member or vertical support flange of the DSX-1 or DSX-3 bay using two provided 12–
24 rack mounting-screws. See

Figure 2

.

14001-B

Figure 2. Bay Tracer Electronic Sensor Device with Mounting Bracket

2. Two sensor cabling options are provided for detecting a change in current on the –48 Vdc

power conductor(s) feeding the bay. If the bay is configured with DSX-only equipment
(option A), proceed to step 2a. If the bay is configured with a mix of DSX and non-DSX
equipment (option B), proceed to step 2b.