Figure 4. sensor cabling option b – ADC P-80-412 User Manual

Page 6

Advertising
background image

ADCP-80-412

N Issue 1 N April 2000

Page 6
© 2000, ADC Telecommunications, Inc.

FILLER

PANEL

SENSOR

ATTACHMENT

INDUCTION

COIL

KEEP NON-DSX

EQUIPMENT

OUT OF COIL

UPPER CABLE TROUGH

POWER

ATTACHMENT

BAYTRACER

FILLER

PANEL

—48V

—48V

BATTERY

RETURN

BATTERY

RETURN

FUSE PANEL

DSX

PANEL

DSX

PANEL

BATTERY RETURN

—48V

BATTERY RETURN

—48V

REAR VIEW

NOTE: SENSOR AND POWER ATTACHMENT POSITION AND
APPEARANCE SHOWN EXAGGERATED FOR CLARITY.

14059-A

Figure 4. Sensor Cabling Option B

4. Attach the trailing wires from the inductive pickup coil to the ADC-provided sensor

connector making sure that the white conductor is routed to the negative (–) pin on the
SENSOR receptacle and the black conductor is routed to the positive (+) pin on the
receptacle. See

Figure 5

.

Caution

: The sensor and power connectors are keyed identically and can be inserted into the

wrong receptacles on the Bay Tracer Electronic Sensor Device. Use care to avoid possible
damage to the sensor.