Site requirement guidelines, Environmental site requirements 31, Beta – Alcatel-Lucent OMNIACCESS 740 User Manual

Page 39

Advertising
background image

Site Requirement Guidelines

Except on the first page, right running head:
Heading1 or Heading1NewPage text (automatic)

31

Alcatel-Lucent

Beta

Beta

OmniAccess 740 Hardware User’s Guide

S

ITE

R

EQUIREMENT

G

UIDELINES

The guidelines in this section help you to maintain and protect your OA-740 and
its components from potential damage from over-voltage, extreme temperature
conditions, and other adverse conditions. To assure normal operation and avoid
unnecessary maintenance, plan your site configuration and prepare your site
before installing the OA-740.

Follow these general precautions when planning your equipment locations and
connections:

•

Make sure that the site maintains an ambient temperature between 15°C and
25°C, and keep the area around the system to be clean and dust-free.

•

Ensure that the cooling vents are not blocked and there is adequate air flow due
to ample clearances around the OA-740.

•

Alcatel-Lucent recommends keeping the OA-740 off the floor and out of any area
that tends to collect dust.

•

Follow ESD prevention procedures to avoid damage to equipment. Damage from
static discharge can cause immediate or intermittent equipment failure.

The table below lists the operating and non-operating environmental site
requirements. The ranges listed are those within which the OA-740 will continue
to operate; however, a measurement that is approaching the minimum or
maximum of a range indicates a potential problem. You can maintain normal
operation by anticipating and correcting environmental anomalies before they
approach minimum or maximum operating range.

Table 18: Environmental Site Requirements

Specification

Minimum

Maximum

Temperature, operating

0°C

45°C

Temperature, non-operating

–25°C

70°C

Humidity (non-condensing), operating

10%

90%

Altitude, operating

Sea level

10,000 ft. (3048 m)

Altitude, non-operating

Sea level

15,000 ft. (4572 m)

Clearance, air intake, and exhaust

20 inches (50.8 cm)

—

Advertising