Micro doubler capacity deployment rules – ADC EDU-409 User Manual
Page 24

Functional Description
150-409-115-05, Issue 5
18
January 26, 2000
EDU-409 List 1
M
ICRO
D
OUBLER
C
APACITY
D
EPLOYMENT
R
ULES
The deployment rules for micro doubler capacity are summarized below:
1
Use
for indoor enclosures.
2
Use
for outdoor enclosures with Full Solar Load for
ambient temperatures up to 46.1 °C maximum.
3
can be increased by two for non-solar
load (shaded or manhole applications).
4
Decrease capacities in
by one for every 2.7 °C increase, or
fraction thereof, in ambient temperatures above 46.1 °C.
5
Increase the capacities by one for every full +2.7 °C reduction in ambient
temperature below 46.1 °C.
6
Decrease any outdoor capacity by one for every four E1 repeaters, or
fraction thereof, that are installed with the doublers.
7
For all outdoor applications, decrease the capacity by one for every two
adjacent doublers that are not separated by at least one empty slot.