Specifications 60

UPS model

Load segment

Output receptacles

2

2 x 5-20T

R/T3000h NA/JPN

1

3 x IEC-320-C13

1 x IEC-320-C19

1 x L6-20R

2

3 x IEC-320-C13

1 x IEC-320-C19

R/T3000 INTL

1

3 x IEC-320-C13

1 x IEC-320-C19

2

3 x IEC-320-C13

1 x IEC-320-C19

Power protection specifications

UPS model

VA

Nominal power rating
(W)

Nominal voltage
setting

R/T3000
NA/JPN

2880

2700

100, 110, 120, 127

R/T3000h
NA/JPN

3300

3000

204, 220, 230, 240

R/T3000 INTL

3300

3000

204, 220, 230, 240

Output tolerance specifications

Source of power

Regulation

Utility power (nominal
range)

-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer
Business Equipment Manufacturers
Association)

Battery power

±5% of nominal output voltage rating

Output feature specifications

Feature

Specification

Online efficiency

94% nominal input voltage

Voltage wave shape

Sine wave; 5% THD with typical PFC load

Surge suppression

300J via MOVs

Noise filtering

EN 55022 line filter for normal and common mode
use