Battery specifications, High-voltage ups battery runtimes, Low-voltage ups battery runtimes – HP Tower Uninterruptible Power System User Manual

Page 61: Environmental specifications

Advertising
background image

Specifications 61

Battery specifications

Feature

Specification

Type

12 V, 5 AH, sealed, maintenance-free, rechargeable, valve
regulated lead-acid batteries with a 3-5 year service life at
25°C (77°F).

Voltage

The battery modules have a battery string voltage of 120 V.

Charging

Complete charge takes no more than 48 hours. After
approximately 3 hours, the batteries reach 80% charge at
default nominal utility voltage and no load.

High-voltage UPS battery runtimes

Load, percent

Estimated battery
runtime

Runtime with one ERM

Runtime with two ERMs

20

40 minutes

125 minutes

225 minutes

50

12 minutes

50 minutes

89 minutes

80

6 minutes

30 minutes

54 minutes

100

4 minutes

24 minutes

43 minutes

Low-voltage UPS battery runtimes

Load, percent

Estimated battery
runtime

Runtime with one ERM

Runtime with two ERMs

20

45 minutes

142 minutes

256 minutes

50

15.5 minutes

55 minutes

99 minutes

80

7 minutes

34 minutes

60 minutes

100

5 minutes

26 minutes

47 minutes

Environmental specifications

Feature

Specification

Operating temperature 10°C to 40°C (50°F to 104°F); UL-tested at 25°C

(77°F)

Nonoperating
temperature

-20°C to 50°C (-4°F to 122°F)

Relative humidity

20% to 80%; noncondensing

Operating altitude

Up to 2,000 m (6,600 ft) above sea level

Nonoperating altitude

15,000 m (49,212 ft) above sea level

Audible noise

Less than 45 dBA, normal operation
Less than 50 dBA, on battery power

Advertising