Installation 22

WARNING:

To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, a

UPS installed in a computer equipment room must be connected to a REPO circuit.

IMPORTANT:

The remote switch must be in the Off (open) position to enable power to the output

receptacles.

NOTE:

Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or

equivalent).

Separate wire pairs are attached to a single, normally-open contact in a parallel connection. HP

recommends using different colors for the positive and negative wires.
If a connector becomes disconnected and is reconnected with reversed polarity, a REPO is initiated. To avoid

REPO port disconnect:

Minimize wire strain while connecting the REPO port.