HP Modular Cooling System Options User Manual

Page 16

Advertising
background image

Web interface 16

Indicators

Meaning

Modules or sensors

Server Intake Temperature, Water Flow Meter

SNMP notification

Critical

Type of message

Alarm

Solution:

1.

Verify the water supply and that the MCS 5042 unit is receiving water.

2.

Verify that the water pressure delta is accurate.

3.

Verify that the water flow loss emergency door opening temperature threshold is not less than 5°C
(41°F) above or more than 20°C (68°F) above the Server Intake Temperature Set Point.

4.

Adjust the temperature in the Server Intake Temperature Set Point or the Water Flow Loss Emergency
Door Opening Temperature Threshold fields to prevent false alarms.

IMPORTANT:

Use caution when entering temperatures in the Emergency Door Opening fields.

Setting the temperature thresholds too low might cause the MCS unit to shut down.

Emergency Door Opening due to High Temperature (35/36/38°C) (95/97/100°F)

Indicators

Meaning

Operator display alarm message Emergency Door, Heat

Web interface alarm message

Emergency Door Opening due to High Temperature (35/36/38°C)

(95/97/100°F)

The interface alarm message displays the temperatures of the fans so that
you can see which temperature has been exceeded and had caused the

alarm.

Condition

The High Temperature Emergency Door Opening Threshold has been
exceeded.

Modules or sensors

Server Intake Temperature

SNMP notification

Critical

Type of message

Alarm

Solution:

1.

Verify the water supply and that the MCS 5042 unit is receiving water.

2.

Verify that the High Temperature Emergency Door Opening Threshold is not less than 5°C (41°F) above
or more than 20°C (68°F) above the Server Intake Temperature Set Point, or that it is not below the

Water Flow Loss Emergency Door Opening Temperature Threshold.

3.

Adjust the temperature in the Server Intake Temperature Set Point or the Water Flow Loss Emergency
Door Opening Temperature Threshold fields to prevent false alarms.

IMPORTANT:

Use caution when entering temperatures in the Emergency Door Opening fields.

Setting the temperature thresholds too low might cause the MCS unit to shut down.

The condensation pump has exceeded x cycles

Indicators

Meaning

Operator display alarm message Excessive moisture

Web interface alarm message

The condensation pump has exceeded x cycles

Advertising
This manual is related to the following products: