Advanced tab – HP Modular Cooling System Options User Manual

Page 27

Advertising
background image

Web interface 27

o

Select Disable to not allow the alarm relay when a temperature alarm is generated.

2.

Select to enable or disable the audible alarm from the Audible Alarm radio buttons. This setting affects
all alarms and warnings, except for the Server Intake Temperature.

o

Select Enable to allow the audible alarm to sound when an alarm is generated.

o

Select Disable to not allow the audible alarm to sound when an alarm is generated.

3.

Select to allow the alarm to be reset (which also resets the audible alarm and alarm relay) automatically
(Auto) or manually (Manual) from the Alarm Reset radio buttons. This setting affects all alarms and
warnings, except for the Server Intake Temperature.

o

Select Auto to allow the alarm to be turned off automatically if the condition returns to a valid range
after an alarm is generated.

o

Select Manual to allow the alarm to be turned off by clicking Clear Alarms in the Setup>General
menu. The alarm can also be cleared by pressing the C key on the management module after any

alarm is generated.

4.

Select the checkbox to deactivate the scheduled alarms for trap receivers 1 through 4.

5.

Do one of the following:

o

Click Save Settings to save the information.

o

Click Cancel to undo the changes.

Advanced tab

This screen contains the Temperature Difference for Heat Load Warning field. This field is used to adjust the

heat load temperature, which is the temperature difference between the highest and lowest Server Exhaust

Temperature. If the heat load temperature difference varies by more than this setting, then a Heat load

warning appears in the operator display, and a Heat Load Warning appears in the web interface. To
disable the warning, set the value to 0.
When the MCS 5042 unit is in Auto mode, the Fan Speed Target and Water Valve fields are not active.

On the Advanced screen, the administrator can change the temperature control modes for the management

module.

IMPORTANT:

Temperature Control Manual mode is for service and troubleshooting only and is

not to be used in a production environment.