HP ProLiant DL360 G6 Server User Manual

Page 111

Advertising
background image

Specifications 111

Rated input current

5.5 A at 100 VAC
2.6 A at 200 VAC

Rated input power

526 W at 100V AC input

505 W at 200V AC input

BTUs per hour

1794 at 100V AC input

1725 at 200V AC input

Power supply output

Rated steady-state power

460 W at 100V to 120V AC input
460 W at 200V to 240V AC input

Maximum peak power

460 W at 100V to 120V AC input
460 W at 200V to 240V AC input

HP ProLiant 750 W Power Supply

Specification

Value

Input requirements

Rated input voltage

100 to 120 VAC, 200 to
240 VAC

Rated input frequency

50 Hz to 60 Hz

Rated input current

8.9 A at 100 VAC
4.3 A at 200 VAC

Rated input power

857 W at 100V AC input
824 W at 200V AC input

BTUs per hour

2925 at 100V AC input

2812 at 200V AC input

Power supply output

Rated steady-state power

750 W at 100V to 120V AC input

750 W at 200V to 240V AC input

Maximum peak power

750 W at 100V to 120V AC input
750 W at 200V to 240V AC input

HP ProLiant 1200 W Power Supply

Specification

Value

Input requirements

Rated input voltage

100 to 120 VAC, 200 to
240 VAC

Rated input frequency

50 Hz to 60 Hz

Rated input current

10 A at 100 VAC
4.9 A at 200 VAC

Rated input power

930 W at 100V AC input
1348 W at 200V AC input

BTUs per hour

3530 at 120V AC input
4600 at 200V to 240V AC input

Power supply output

Rated steady-state power

800 W at 100V AC input

900 W at 120V AC input
1200 W at 200V to 240V AC

input

Advertising