Thermal and air flow performance, Environmental specifications, Hp 642 1200mm rack specifications – HP Modular Cooling System User Manual

Page 58

Advertising
background image

Specifications 58

Thermal and air flow performance

Maximum thermal and air flow

performance parameters

Single rack

Dual rack
(Specification per rack)

Air temperature—Inlet to rack-mounted

components

25ºC (68ºF)

25ºC (68ºF)

Chilled water temperature

7º–18°C (45º–64°F)

7º–18°C (45º–64°F)

Total rack-mounted component air flow 4,500 cfm (7,650 m3/h) or less at

0 or more pressure drop across the

rack mounted components

2,400 cfm (4,050 m3/h) or less at
0 or more pressure drop across the

rack mounted components

Chilled water flow rate

124 l/min (32.8 US gal/min)

124 l/min (32.8 US gal/min)

Chilled water pressure differential at
flow needed to meet thermal

specifications

1.0 bar delta pressure

1.0 bar delta pressure

Heat lost to room

Approximately 10% maximum

depending on the MCS settings
and room temperature

Approximately 10% maximum

depending on the MCS settings
and room temperature

Server heat load

50 kW maximum

25 kW maximum

Environmental specifications

Features

Specifications

Operating temperature:

Recommended
Allowable

18ºC (64.4ºF) to 27ºC (80.6ºF)

15ºC to 32ºC (59ºF to 90ºF)

Non-operating temperature 0ºC to 60ºC (32ºF to 140ºF)
Transit temperature

-30ºC to 60ºC (-22ºF to 140ºF), up to 72 hours

Storage temperature

-20ºC to 60ºC (-4ºF to 140ºF)

Operating humidity:
Recommended minimum

Recommended maximum

Allowable range

5.5°C (41.9°F) dew point
60% relative humidity and 15°C (59°F) dew point

20 to 80% relative humidity (non-condensing)

Non-operating humidity

5 to 95% relative humidity (non-condensing)

Operating altitude

-76.2 to 3,048 m (-250 to 10,000 ft)

Non-operating altitude

-76.2 to 9,144 m (-250 to 30,000 ft)

NOTE:

For safety, the MCS-200 unit is equipped with a dew point sensor and control system

which creates an alarm that sounds if the chilled water temperature is lower than the dew point

temperature. This condition might create excessive condensation on the heat exchanger.
Therefore, the unit must be operated in non-condensing operating conditions.

HP 642 1200mm Rack specifications

U height

Width

Depth

Dynamic load (gross)

Static load

42U

598 mm
(23.8 in)

1,300 mm
(47.24 in)

1,043 kg
(2,300 lb)

1,361 kg
(3,000 lb)