CMP PXRC-REX User Manual

Cable gland, Cable gland type pxrc-rex type pxrc-rex

Advertising
background image

INSTALLATION INSTRUCTIONS FOR

CMP CONDUIT GLAND TYPE PXRC-REX

BARRIER CABLE GLAND FOR USE IN HAZARDOUS AREAS WITH BRAID, UNARMOURED CABLE OR

INDIVIDUAL CORES HOUSED IN CONDUIT.

INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 94/9/EC

CM

P

Do

cu

m

en

tN

o.

FI

41

5

Is

su

e

5

01

/1

3

0518

Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS

Tel: +44 191 265 7411 • Fax: +44 191 265 0581

E-Mail: [email protected] • Web: www.cmp-products.com

Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.

I, the undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEX Directive 94/9/EC and the

following standards:-

EN60079-0:2009, EN60079-1:2007, EN60079-7:2007, BS 6121:1989, EN50262:1998 (Amd 2011), EN61241-0:2004, EN61241-1:2004

Dr Geof Mood - Technical Director - (Authorised Person)

DUBAI

• HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH

www.cmp-products.com

Ca

bl

e

Gl

an

d

Se

le

ct

io

n

Ta

bl

e

Logo’s shown for illustration purposes only. Please check certification for details

CABLE GLAND

CABLE GLAND

TYPE PXRC-REX

TYPE PXRC-REX

Cable

Gland

Size

Available Entry Threads

Minimum

Thread

Length

Standard

Female

Connection

Thread

Diameter

Over

Conductors

Number

Of

Cores

Overall

Cable

Diameter

Across

Flats

Across

Corners

Nominal

Protrusion

Length

Ordering Reference

(Brass Metric M X F)*

Cale Gland Weight

(Kgs)

Standard

Option

Metric

NPT

NPT

Max

Max

Max

Max

20

M20

1/2”

3/4”

15.0

1/2”

12.6

21

13.9

27.0

29.7

24.0

20PXRCREX1RA031

0.100

25

M25

3/4”

1”

15.0

3/4”

17.5

38

19.9

36.0

39.6

26.0

25PXRCREX1RA032

0.250

32

M32

1”

1-1/4”

15.0

1”

23.6

59

26.2

41.0

45.1

27.0

32PXRCREX1RA033

0.460

40

M40

1-1/4”

1-1/2”

15.0

1-1/4”

30.0

89

32.3

50.0

55.0

28.0

40PXRCREX1RA034

0.615

50S

M50

1-1/2”

2”

15.0

1-1/2”

36.6

115

38.9

55.0

60.5

29.0

50SPXRCREX1RA035

0.710

50

M50

2”

2-1/2”

15.0

2”

41.0

115

44.2

60.0

66.0

30.0

50PXRCREX1RA036

0.700

63S

M63

2”

2-1/2”

15.0

2”

47.9

140

50.0

70.0

77.0

30.0

63SPXRCREX1RA036

0.850

63

M63

2-1/2”

3”

15.0

2-1/2”

53.7

140

58.0

75.0

82.5

30.0

63PXRCREX1RA037

0.820

75S

M75

2-1/2”

3”

15.0

2-1/2”

59.9

140

62.4

79.0

86.9

32.0

75SPXRCREX1RA037

1.100

75

M75

3”

3-1/2”

15.0

3”

64.3

140

68.1

84.0

92.4

32.0

75PXRCREX1RA038

1.090

90

M90

3”

3-1/2””

15.0

3-1/2”

75.3

140

80.1

108.0

118.8

44.0

90PXRCREX1RA038

1.500

All dimensions in millimetres unless otherwise stated

* Please specify MALE & FEMALE threads requires when ordering

TECHNICAL DATA

CABLE GLAND TYPE

: PXRC-REX

INGRESS PROTECTION

: IP66 minimum

PROCESS CONTROL SYSTEM

: BS EN ISO 9001

: ISO/IEC 80079-34:2011

HAZARDOUS AREA CLASSIFICATION

ATEX CERTIFICATION No

: SIRA 06ATEX1097X

ATEX CERTIFICATION CODE

:

II 2 GD Ex d IIC / Ex e II / Ex tD A21 IP66

IEC Ex CERTIFICATION No

: IEC Ex SIR.06.0044X

IEC Ex CERTIFICATION CODE

: Ex d IIC / Ex e II / Ex tD A21 IP66

INSTALLATION INSTRUCTIONS

Installation should only be performed by a competent person using the correct tools. Spanners should be used for tightening. Read all instructions

before beginning installation.

SPECIAL CONDITIONS FOR SAFE USE

1. The cable gland ranges shall only be used where the temperature, at the point of entry, is in the following ranges:

-60°C to +85°C.

2. The entry component threads may need additional sealing to maintain the ingress protection ratings as applicable to the associated equipment to

which it is attached.

ACCESSORIES

The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-

Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer | Shroud

Advertising