Aurora Electronics MAGNETEK PVI-3600-OUTD-UK-F-W User Manual

Page 59

Advertising
background image

Installation and Operator’s Manual

Page 59 of 63

(PVI-3600-OUTD-UK-F-W Rev.: 1.0)

Description

Value

PVI-3600-OUTD-UK-F-W

Nominal input voltage

360Vdc

Minimum input voltage to
connect to the grid

50Vdc

“Absolute Maximum Rating”
for input voltage

600Vdc

Input voltage, MPPT operating
range

50Vdc to 530Vdc

Input voltage, MPPT range at
full power

200Vdc to 530Vdc

Max. operating input current
(Wind MPPT Input)

20Adc

Max. input power
(Wind MPPT Input)

3800 W

DC Ground fault protection

Ground fault detection and shut off of

utility-interactive inverter

MPPT configuration

Single Wind MPPT , Power Curve is specific to

the Wind Turbine model


As stated above, AURORA Wind performs MPPT on the programmed Wind
turbine power curve and constantly researches the max. input Dc power point. This
process is called MPPT (Maximum Power Point Tracking).

NOTE: If the input current supplied by the Wind Interface Box
connected to the inverter is above the max. value and the input voltage is

within the allowed range, the inverter is not damaged.

Advertising