Installation

20

900-0144-01-01 Rev A

DC Wiring

WARNING: Shock Hazard

Use caution when working in the vicinity of the inverter’s battery terminals.

CAUTION: Equipment Damage

Never reverse the polarity of the battery cables. Always ensure correct polarity.

CAUTION: Fire Hazard

The installer is responsible for providing overcurrent protection. Install a

circuit breaker or overcurrent device on each DC positive (+) conductor to

protect the DC system.

Never install extra washers or hardware between the mounting surface
and the battery cable lug. The decreased surface area can build up heat.

See the hardware diagrams on page 21.

IMPORTANT:

Table 4 contains OutBack’s recommendations for minimum cable sizes.

Other codes may supersede OutBack’s requirements. Consult local codes

for final size requirements.

Figure 15 GS7048E and GS3548E Battery Terminals

The Radian inverter has four battery cable terminals, two positive

and two negative. Each terminal is a threaded hole which accepts

a hex bolt (provided). Notes on assembly and cabling are shown

on the next page.

IMPORTANT:

The Radian GS7048E contains two internal power modules, each with its own
set of DC terminals. Both sets of terminals

must be connected to battery

power for the inverter to work correctly.

The Radian GS3548E contains a single power module which occupies the

space on the left. Although it has two pairs of terminals, only the pair on the

left is functional. The battery cables must be connected to these terminals.

The terminals on the right

must not be connected to battery power.

GS7048E

GS3548E