AC Wiring

WARNING: Shock Hazard

Ensure there is no more than one AC neutral-ground bond at any time. Local

or national codes may require the bond at the main panel only.

The GSLC is equipped with its own bond, which may need to be removed.

IMPORTANT

:

The installer is responsible for providing overcurrent protection. The AC input and

output must be protected with branch-rated circuit breakers of up to 50 Aac

maximum size to meet local code requirements.

The Radian inverter/charger’s AC terminal block has six positions for AC wires. The minimum
recommended size is 10 mm

2

or #8 AWG (0.013 in

2

). Larger wire gauges may be required for specific

conditions. The largest size that can be used with the terminals is 16 mm

2

or #6 AWG (0.021 in

2

) wire.

The inverter makes its AC connections using spring-loaded clamps. It is necessary to strip

approximately 1.3 cm (½ inch) of insulation from the end of each wire. Other tools are not required.

Figure 17 AC Terminals

The terminals labeled

L are used to connect to the “hot” or “line” wires. All system wiring must

comply with national and local codes and regulations.
Three neutral (

N) terminals are available. These terminals are electrically common. Any of them can

be used to connect to neutral wires from various parts of the system. The most common connections

are to the neutral bus on the main panel or utility grid service, the neutral bus on the output load

panel, the neutral bus in the GSLC, and the neutral wire from a generator.
The Radian can accept input voltages that range between (nominal) 220 Vac, 230 Vac, or 240 Vac

(single-phase only). The range of input acceptance may need to be adjusted to the nominal voltage of

the system so that inappropriate voltages are not accepted. The AC source(s) can power both battery

charger and loads if sized correctly. Use the source amperage and the charger size to determine

actual maximum draw. Size the input circuit breakers according to these specifications.
The terminals labeled

OUT are used to connect the inverter to the load circuits. These terminals also

transfer power from an AC source if it is available. Size the load circuit breakers accordingly.

Generator In (Line and Neutral)

AC Out

(Line and

Neutral)

Grid In (Line

and Neutral)