Radian series, Installation, Ac wire sizes and torque values – Outback Power Systems GS4048A Quick Start Guide with GSLC User Manual

Page 2

Advertising
background image

Installation

900-0162-01-00 Rev A.vsd\Page-2\2014-01-24

©2014 OutBack Power Technologies. All Rights Reserved.

RADIAN Series

16" (40.6 cm)

Plywood (Optional)

Wall Board

Wall

Stud

Wall Bracket

Wall

Stud

4.1"

(10.4 cm)

5.0"

(12.7 cm)

6.0"

(15.2 cm)

8.0"

(20.3 cm)

AC Circuit Breakers

1

GFDI

2
3
4

DC Terminals - Inverter

AC Terminals - Inverter

5

DC Circuit Breakers

6

PV Circuit Breakers

Charge Controller Terminals

7
8

Mechanical Interlock (Bypass)

9

10

Communication Ports

Auxiliary Terminals

11
12
13
14
15

AC OUT Bus Bar L1

16
17
18
19

AC OUT Bus Bar L2

GRID IN Bus Bar L1

GRID IN Bus Bar L2

GEN IN Bus Bar L1

GEN IN Bus Bar L2

AC Neutral

Ground

20

DC Positive (+) Plate (not used
on GSLC175PV1-120/240)

PV Negative (–) Terminals

21
22

PV Positive (+) Bus Bars

DC Negative (–) Plate (GS-SBUS)

N
E
U

L1 L2

GRID

L1 L2

GEN

N
E
U

N
E
U

L1 L2

OUT

RELAY

AUX

+ -

12V
AUX

Switch

INV

Remote

Battery

Temp

FM80 #1 FM80 #2

MATE3

HUB

10.3

GS8048A

GSLC175-PV-120/240

1

2

2

3

4

5

7

8

8

9

9

9

9

9

10

10

10

6

ON/OFF

INV

11

12

13

14

15

16

17

18

19

20

21

21

22

20

AC Wire Sizes and Torque Values

OutBack recommends that conductors be

#6 AWG THHN copper, or larger, rated to 75°C

(minimum) unless local code requires otherwise.

AWG

In-lb

#14 to #10

20

#8

25

#6 to #4

35

#3

35

#2

40

#1

50

1/0

50

mm

2

2.5 to 6

10

16 to 25

35

35

50

70

Nm

2.3

2.8

4.0

4.0

4.5

5.6

5.6

Wire Size

Torque

Torque Requirements

Plywood

(Optional)

Wall Board

Wall

Bracket

Wall Stud

N
E
U

L1 L2

GRID

L1 L2

GEN

N
E
U

N
E
U

L1 L2

OUT

RELAY

AUX

+ -

12V
AUX

Switch

INV

Remote

Battery

Temp

ON/OFF

INV

28.0"

(71.1 cm)

16" (40.6 cm)

0.5" (1.3 cm)

0.5" (1.3 cm)

29.1"

(74.0 cm)

45.0"

(114.3

cm)

13.7"

(34.8 cm)

Inverter
Bracket

8.75"

(22 cm)

Circuit Breaker

Stud

Torque

In-lb

Nm

M8

20

2.3

¼ - 20

35

4.0

5/16 - 18

50

5.6

3/8 - 16

225

25.4

DC Plates

Torque

In-lb

Nm

Upper holes (+)

Shunt Bolts (–)

and GS-SBUS

Lower holes (+)

60

6.8

5.6

6.8

60

50

60

Minimum DC Cable based on

the DC Circuit Breaker

Torque

In-lb

Nm

50

5.6

225

25.4

225

25.4

Circuit

Breaker

Cable Size

125

1/0 (70 mm

2

)

175

2/0 (70 mm

2

)

250

4/0 (120 mm

2

)

35

4.0

80

#4 AWG (25 mm

2

)

35

4.0

60

#6 AWG (16 mm

2

)

Positive Battery Cable Connections

CAUTION:

Equipment Damage
When connecting cables
from the Radian inverter
to the battery terminals,
make sure to observe
the proper polarity.
Connecting the cables
incorrectly can damage
or destroy the equipment
and void the product
warranty.

Ensure the mounting surface is strong enough to handle 3 times the total weight of all the components. Add plywood or other
reinforcing material as necessary to strengthen the surface.

Attach the wall bracket. Center the mounting holes on the wall studs. Use all 6 mounting screws to secure the bracket.

Lift the inverter so that the inverter bracket is above the wall bracket.

Lower the inverter so that the inverter bracket slips into the wall bracket.
If GSLC is not used: Secure the inverter to the surface using a minimum of 1 wall screw (or appropriate hardware).
If GSLC is used: Unscrew the inverter bottom screws approximately ¼” (0.6 cm) to 3/16" (0.5 cm).
Align the GSLC along the bottom of the inverter. Slide the bottom screws into the keyhole slots.

Mark the spots for the GSLC mounting feet. (If necessary, remove the GSLC to install wall anchors.) Install screws to secure the feet.

Follow the appropriate instructions for installing other components. Different mounting locations are available.

1

3
4

2

5
6
7
8

9

Keyhole Slots

1

2

3

4

5

6

7

The FLEXmax charge
controller is mounted
with the FW-CCB bracket.
The FW-CCB2 allows two
controllers side by side (using
the forward holes to allow for
conduit.)

The Radian has two sets of
bracket positions. The GSLC
has one set.
NOTE: The FLEXmax
Extreme charge controller
attaches directly to the wall,
not the Radian system.

It does not use
OutBack brackets.

14.0"

(35.6 cm)

12.0"

(31.8 cm)

8

9

FN-DC

The Radian allows two locations
for the MATE3 mounting bracket
(FW-MB3).

The Radian has one
mounting location for the
HUB product. The GSLC
also has one location.

Left Side:

Right Side:

For GSLC door
clearance, space
systems 0.9"
(3.2 cm) apart.

When

stacking

multiple

inverters:

N
E
U

L1 L2

GRID

L1 L2

GEN

N
E
U

N
E
U

L1 L2

OUT

1

Wiring to AC terminals is
displayed on the Wiring page.

FN-DC wiring is displayed
on the Wiring page.

Bottom
Screws

19

Negative Battery Cable

Connections

Green

> 90% (blinks if charge parameters

are met)

Color

Red

Yellow

Yellow

Yellow

≥ 80%

≥ 70%

≥ 60%

≥ 60% off, < 60% solid, < 50% blinks

Battery State of Charge

FN-DC LED Indicators

Bolt 3/8"

DC

Positive

(+) Plate

Battery

Positive

(+) Lug

Flat

Washer

Nut

Lock

Washer

Flat

Washer

Shunt

Bolt 3/8"

Lock

Washer

Flat

Washer

Battery

Negative

(–) Lug

DC

Negative (-)

Plate

(GS-SBUS)

GSLC175-PV-120/240

GSLC175PV1-120/240

DC Disconnect

Stud

Battery

Positive

(+) Lug

FM80

Positive (+)

Terminal

Flat

Washer

Nut

Lock

Washer

FN-DC

Positive (+)

Sense

Terminal

4

22

20

20

!