Installation requirements, Gas supply system, Gas pressure requirements – State SBN85 390NE A User Manual

Page 12: Supply gas regulator, Power supply, Water temperature control and mixing valves

Advertising
background image

12

addition adjustment maybe required later to maintain a

steady gas supply pressure.

4. When installing multiple water heaters in the same gas

supply system it is recommended that individual positive

lock-up gas pressure regulators be installed at each unit.

power supply

The water heaters covered in this manual require a 120 VAC,

1Ø (single phase), 60hz, 15 amp power supply and must also

be electrically grounded in accordance with local codes or, in the

absence of local codes, with the National electrical Code, ANSI/

NFPA 70 or the Canadian electrical Code, CSA C22.1.

water temperature Control and mixing ValVes

Water temperature over 125°F (52°C)

can cause severe burns instantly

resulting in severe injury or death.
Children, the elderly and the

physically or mentally disabled are at

highest risk for scald injury.
Feel water before bathing or

showering.
Temperature limiting devices such as

mixing valves must be installed

when required by codes and to

ensure safe temperatures at fixtures.

Water heated to a temperature which will satisfy clothes washing,

dish washing, and other sanitizing needs can scald and cause

permanent injury upon contact. Short repeated heating cycles

caused by small hot water uses can cause temperatures at the

point of use to exceed the water heater’s temperature setting by

up to 20°F (11°C).
Some people are more likely to be permanently injured by

hot water than others. These include the elderly, children, the

infirm and the physically/mentally disabled. Table 6 shows the

approximate time-to-burn relationship for normal adult skin.

If anyone using hot water provided by the water heater being

installed fits into one of these groups or if there is a local code

or state law requiring a certain water temperature at the point of

use, then special precautions must be taken.
In addition to using the lowest possible temperature setting that

satisfies the demand of the application a Mixing Valve should be

installed at the water heater (see Figure 10) or at the hot water

taps to further reduce system water temperature.
Mixing valves are available at plumbing supply stores. Consult

a Qualified Installer or Service Agency. Follow mixing valve

manufacturer’s instructions for installation of the valves.

taBle 6.

Water Temperature

°F (°C)

Time for 1st Degree Burn

(less Severe Burns)

Time for Permanent Burns

2nd & 3rd Degree

(Most Severe Burns)

110 (43)

(normal shower temp.)

116 (47)

(pain threshold)

116 (47)

35 minutes

45 minutes

122 (50)

1 minute

5 minutes

131 (55)

5 seconds

25 seconds

140 (60)

2 seconds

5 seconds

149 (65)

1 second

2 seconds

154 (68)

instantaneous

1 second

(U.S. Government Memorandum, C.P.S.C., Peter l. Armstrong, Sept. 15, 1978)

gas supply system

low pressure building gas supply systems are defined as those

systems that cannot under any circumstances exceed 14”

W.C. (1/2 PSI Gauge). These systems do not require pressure

regulation. Measurements should be taken to insure that gas

pressures are stable and fall within the requirements stated on the

water heater rating plate. readings should be taken with all gas

burning equipment off (static pressure) and with all gas burning

equipment running at maximum rate (dynamic pressure). The gas

supply pressure must be stable within 1.5” W.C. from static to

dynamic pressure to provide good performance. Pressure drops

that exceed 1.5” W.C. may cause rough starting, noisy combustion

or nuisance outages. Increases or spikes in static pressure during

off cycles may cause failure to ignite or in severe cases damage to

appliance gas valves. If your low pressure system does NOT meet

these requirements, the installer is responsible for the corrections.
high Pressure building supply systems use pressures that exceed

14” W.C. (1/2 PSI Gauge). These systems must use field supplied

regulators to lower the gas pressure to less than 14” W.C. (1/2 PSI

Gauge). Appliances require gas regulators that are properly sized

for the water heater input and deliver the rating plate specified

pressures. Gas supply systems where pressure exceeds 5 PSI

often require multiple regulators to achieve desired pressures.

Systems in excess of 5 PSI building pressure should be designed

by gas delivery professionals for best performance. Water heaters

connected to gas supply systems that exceed 14” W.C. (1/2 PSI

Gauge) at any time must be equipped with a gas supply regulator.

gas pressure reQuirements

All models require a minimum gas supply pressure of 5.2” W.C.

The minimum supply pressure is measured while gas is flowing

(dynamic pressure). The supply pressure (dynamic) should never

fall below 5.2” W.C. The supply pressure should be measured

with all gas fired appliances connected to the common main

firing at full capacity. If the supply pressure drops more than 1.5”

W.C. as gas begins to flow to the water heater then the supply

gas system including the gas line and/or the gas regulator may

be restricted or undersized. See Supply Gas regulator section

and Gas Piping section of this manual. The low gas pressure

switch will shut down the water heater if the supply gas pressure

drops below the minimum allowable value.
The gas valve on all models has a maximum gas supply pressure

limit of 14" W.C. The maximum supply pressure is measured

while gas is not flowing (static pressure).

supply gas regulator

The maximum allowable gas supply pressure for this water

heater is 14.0 inches W.C. (3.48 kPa). Install a positive lock-up

gas pressure regulator in the gas supply line if inlet gas pressure

can exceed 14.0 inches W.C. (3.48 kPa) at any time.
If a positive lock-up regulator is required follow these instructions:
1. Positive lock-up gas pressure regulators must be rated at or

above the input Btu/hr rating of the water heater they supply.

2. Positive lock-up gas pressure regulator(s) should be installed no

closer than 3 feet (1 meter) and no farther than 8 feet (2.4 meters)

of equivalent length from the water heater’s inlet gas connection.

3. After installing the positive lock-up gas pressure regulator(s)

an initial nominal supply pressure setting of 7.0” W.C.

while the water heater is operating is recommended and

will generally provide good water heater operation. Some

installation reQuirements

Advertising