Vaisala XMW90 User Manual

Bacnet pics xmw90 series

Advertising
background image

BACnet PICS

XMW90 Series

M211586EN-D _______________________________________________________________________ 1

BACNET PROTOCOL IMPLEMENTATION

CONFORMANCE STATEMENT

XMW90 series transmitters are wall-mount transmitters for building automation

applications. XMW90 series includes transmitter models for measuring humidity, carbon

dioxide, and temperature.

Date

March 7, 2014

Vendor Name

Vaisala Oyj

Product Name

XMW90

Product Model Numbers

HMW95 | GMW95 | GMW95R

Applications Software Version

1.1.28 and later

Firmware Version

1.1.0.0 and later

BACnet Protocol Revision

Version 1, Revision 4

BACnet Standardized Device Profile

(Annex L)

BACnet Operator Workstation (B-OWS)

BACnet Building Controller (B-BC)

BACnet Advanced Application Controller (B-AAC)

BACnet Application Specific Controller (B-ASC)

BACnet Smart Sensor (B-SS)

BACnet Smart Actuator (B-SA)

List of all BACnet Interoperability

Building Blocks Supported

(Annex K)

DS-RP-B, DS-RPM-B, DS-WP-B, DS-COVU-B,

DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-RD-B

Segmentation Capability

Segmentation Requests Supported

Segmentation Responses Supported

Standard Object Types Supported

Analog Input

Analog Output

Analog Value

Averaging

Binary Input

Binary Output

Binary Value

Calendar

Command

Device

Event Enrollment

File

Group

Life Safety Point

Life Safety Zone

Loop