Chapter 5 ________________________________________ Advanced Use of Lizard Setup Software
VAISALA______________________________________________________________________ 151
0905-088
Figure 72
Activating Years to Configure Window
b.
In the References used to start/end times window, shown in
above, you can choose Local or UTC
as the reference used. Local means that daylight saving
starting and ending times follow local time. UTC means that
starting and ending times follow UTC time. For example, in
USA, daylight saving times are implemented in local time,
whereas in Europe, they are implemented in UTC time.
4.
In the Configure year window, select the year for which to
configure the start and end days by using the arrow buttons.
5.
Set the start day for daylight saving time like this:
a.
Set the month when the daylight saving time starts by using
the left and right arrow buttons until you reach the correct
month. For instance, September.
b.
Set the day when the daylight saving time starts by clicking on
the day box. For instance, 11.
c.
Set the time of day when the daylight saving time starts by
typing the hours, minutes, and seconds in their respective
boxes. For instance, if the daylight saving time starts at 2
o'clock in the morning sharp, type Hour: 2, Minute: 0, and
Second: 0.
6.
Set the end day for daylight saving time by repeating the actions in
step 5.
7.
Exit the daylight saving time configuration by closing the
configuration window. Save the settings by clicking the Save
Setup button in the upper right corner of the Configure setup
window.