Red Lion TCU User Manual
Page 75
Advertising

ON/OFF and PID control can be used for the heat and cool outputs in
several combinations.
The following lists the valid control modes:
OP1 & OP2 VALID CONTROL MODES
OP1
MODE
OP2
MODE
MANUAL MODE
OUTPUT POWER
RANGE
OP1
STATE
OP2
STATE
PID
—
0% to +100%
OP1-TP
—
ON/OFF
PrOP = 0.0
—
100
OP1-ON
—
Any other setting
OP1-OFF
—
PID
PID
-100% to +100%
OP1-TP
OP2-TP
PID
ON/OFF
(GAN2=0.0)
0% to +100%
OP1-TP
OP2-OFF
-100% to 0%
OP1-TP
OP2-ON
ON/OFF
(PrOP=0.0)
ON/OFF
(GAN2=0.0)
+100%
OP1-ON
OP2-OFF
-100%
OP1-OFF
OP2-ON
Any other setting
OP1-OFF
OP2-OFF
TP - Time Proportioning
Note: In manual mode, the % output power is not limited to the output
power limits (OPLO & OPHI)
67
Figure 38, OP1/OP2 On/Off Action
Advertising