Red Lion IFMR User Manual

Page 7

Advertising
background image

7

For Overspeed operation, the Relay Trip point is internally set to the Trip Frequency plus the

Offset value. For Underspeed operation, the Relay Trip point is internally set to the Trip Frequency
minus the Offset value. The Offset value is equal to the Trip Frequency multiplied by the selected
Offset percentage.
Example: The Offset value is calculated as shown below.
Trip Frequency

= 250 Hz

Rotary Switch Setting = 4 (2.00%)
Offset Value

= 250 Hz x 2.00% (0.02) = 5 Hz

Trip

Point:

OVERSPEED

= 250 + 5 = 255 Hz

UNDERSPEED

= 250 - 5 = 245 Hz

5.1 Place DIP switch 4 to the ON position and DIP switches 5, 6, and 7 as shown.
5.2 The Green input LED blinks the existing setting (see following list), pauses and repeats.

Setting Percentage

0

0.00% (NO Offset)

1 0.25%

(0.0025)

2 0.50%

(0.0050)

3 1.00%

(0.0100)

4 2.00%

(0.0200)

5 5.00%

(0.0500)

6 10.00%

(0.1000)

7 20.00%

(0.2000)

8 25.00%

(0.2500)

9 33.33%

(0.3333)

5.3 Press the push-button. The Green input LED blinks rapidly. Trip Point Offset setting is now

accessed.

5.4 Turn the rotary switch to the selected numerical value for Trip Point Offset desired (see list in

Step 5.2).

5.5 Press the push-button. The Green input LED blinks the value entered, pauses, and repeats the

new setting.

If the new Trip Point Offset setting is acceptable, this section is complete

*

.

If the new Trip Point Offset setting is not the desired setting, repeat Steps 5.3, 5.4, and 5.5.

If the Red relay LED blinks, the rotary switch numerical value is invalid. Repeat Steps 5.4

and 5.5.

*

Section complete; place DIP switch 4 to the down position for normal operation, or change DIP

switches 5, 6, and 7 for the next Configuration Section.

6.0 Set Relay Release Point (Hysteresis)

5.0 Set Relay Trip Point (Offset)

For Overspeed operation, the Relay Release point is set to the Relay Trip point minus the

Hysteresis value. For Underspeed operation, the Relay Release point is set to the Relay Trip point
plus the Hysteresis value. The hysteresis value is calculated by multiplying the hysteresis
percentage by the current trip frequency. If No Hysteresis (setting = 0) is selected, the Relay Trip
and Release points are identical, which can lead to chattering or cycling of the relay at input
frequencies hovering around the Relay Trip point.

Example: Using the Trip Frequency and Offset value as shown in the example above, the

hysteresis value is calculated as shown below.

Rotary Switch Setting = 3 (1.00%)
Hysteresis Value

= 250 Hz x 1.00% (0.01) = 2.5 Hz

Release

Point:

OVERSPEED

= 250 + 5 - 2.5 = 252.5 Hz

UNDERSPEED

= 250 - 5 + 2.5 = 247.5 Hz

6.1 Place DIP switch 4 to the ON position and DIP switches 5, 6, and 7 as shown.
6.2 The Green input LED blinks the existing setting (see following list), pauses, and repeats.

Setting Percentage

0

0.00% (NO Hysteresis)

1

0.25%

(0.0025)

2

0.50%

(0.0050)

3

1.00%

(0.0100)

4

2.00%

(0.0200)

5

5.00%

(0.0500)

6

10.00%

(0.1000)

7

20.00%

(0.2000)

8

25.00%

(0.2500)

9

33.33%

(0.3333)

6.3 Press the push-button. The Green input LED blinks rapidly. Trip Point Hysteresis setting is

now accessed.

6.4 Turn the rotary switch to the selected numerical value for Hysteresis desired (see list in Step 6.2).
6.5 Press the push-button. The Green input LED blinks the value entered, pauses and repeats the

new setting.

If the new Trip Point Hysteresis setting is acceptable, this section is complete

*

.

If the new Trip Point Hysteresis setting is not the desired setting, repeat Steps 6.3, 6.4, and 6.5.

If the Red relay LED blinks, the rotary switch numerical value is invalid. Repeat Steps 6.4

and 6.5.

*

Section complete; place DIP switch 4 to the down position for normal operation, or change DIP

switches 5, 6, and 7 for the next Configuration Section.

5

4

7

6

5

4

7

6

Step 5.2

Step 5.1

Step 6.2

Step 6.1

0

9

8

7 6 5 4

3

2

1

Setting ‘9’

Selected

0

9

8

7 6 5 4

3

2

1

Setting ‘9’

Selected

LED

LED

OUTPUT

RED

GREEN

INPUT

BLINKS

OFF

IN

OUT

LED

LED

OUTPUT

RED

GREEN

INPUT

BLINKS

OFF

IN

OUT

PUSH-BUTTON

OUT

IN

STATUS

Step 5.3

PUSH-BUTTON

OUT

IN

STATUS

Step 6.3

ROTARY

SWITCH

OUT

IN

STATUS

Step 5.4

ROTARY

SWITCH

OUT

IN

STATUS

Step 6.4

Advertising