Red Lion IAMS User Manual
Page 14
Advertising

13
Visualisation of sensor error detection and
input signal outside range
Sensor error check:
Setup
Sensor error detection:
R1, ERR.ACT=NONE R2, ERR.ACT=NONE,
OUT.ERR=NONE
OFF
Else:
ON
Outside range readout (IN.LO, IN.HI):
If the valid range of the A/D converter or the polynomial is exceeded
Input
Range
Readout
Limit
VOLT
0...1 V / 0.2...1 V
IN.LO
< 25 mV
IN.HI
> 1.2 V
0...10 V / 2...10 V
IN.LO
< 25 mV
IN.HI
> 12 V
CURR
0...20 mA / 4...20 mA
IN.LO
< 1.05 mA
IN.HI
> 25.05 mA
LIN.R
0...800
Ω
IN.LO
< 0
Ω
IN.HI
> 1075
Ω
0...10 k
Ω
IN.LO
< 0
Ω
IN.HI
< 110 k
Ω
POTM
IN.LO
< 0.5 %
IN.HI
> 100.5 %
TEMP
TC / RTD
IN.LO
< temperature range 2°C
IN.HI
> temperature range +2°C
Advertising