Red Lion PAXCDC5 (PROFIBUS) User Manual

Description, Specifications, Ordering information

Advertising
background image

1

DESCRIPTION

The PAX PROFIBUS-DP Communications Option Card provides a direct

connection for a PAX panel meter to a PROFIBUS-DP Network. This allows a
PROFIBUS Master device, such as a PLC, to control and monitor the operation
of the PAX meter. The meter functions as an intelligent PROFIBUS-DP Slave
device on the Network.

The PROFIBUS-DP Network connects through a 9-pin D-subminiature

female connector on the rear of the card. The card is installed in the PAX meter
using a slotted rear cover, allowing the PROFIBUS-DP Connector to extend
beyond the rear of the PAX case. Power for the card is provided internally from
the power supply of the PAX meter. The PROFIBUS-DP Network is isolated
from the control electronics on the card using high-speed optocouplers.

This fully featured communications card supports Automatic Baud Rate

Detection, with an operating range of 9.6 Kbaud up to 12 Mbaud. The Station
Address is set via rotary switches. The card’s address is read at power up.

MODEL PAXCDC - PROFIBUS-DP COMMUNICATIONS OPTION CARD

MICRO

DP

DATA

WD

PROFIBUS-DP

CONNECTOR

CONTROLLER

DIAGNOSTIC

LEDs

R0TARY

SWITCHES

(ON BACK)

Data Exchange with the Master device occurs through cyclic I/O data

transmission. The size of the I/O data block is determined by the selection of
pre-configured Modules for the specific PAX meter type. All data values are in
32-bit integer format, Motorola byte ordering. The PROFIBUS-DP protocol per
EN 50170 is implemented using the Siemens SPC3 ASIC. Three on-board
Diagnostic LEDs indicate the status of Data Exchange (DATA), the SPC3
Watchdog (WD) and DP State Machine (DP).

PNO Conformance and GSD File

The PAX PROFIBUS-DP Card is PNO certified, having passed the

conformance test for PROFIBUS-DP Slave devices, Certificate No. Z01170.
The PNO Identifier for this PROFIBUS device is 0x09D0. The functional
characteristics are described in GSD file REDL09D0.GSD. The GSD file and
PAX bitmap can be downloaded from the Red Lion Controls website.

SPECIFICATIONS

1. FIELDBUS TYPE: PROFIBUS-DP per standard EN 50170, implemented

with Siemens SPC3 ASIC

2. BUS INTERFACE: Isolated RS485 through 9-Pin D-Sub connector
3. NETWORK ISOLATION: 500 Vrms for 1 minute (50 V working) between

PROFIBUS-DP network and PAX Sensor & User Input commons. Not
isolated from other PAX option card commons.

4. POWER: Card powered internally by the PAX meter
5. OUTPUT POWER: +5 VDC @ 90 mA max. available on the D-Sub

connector pins 5 (GND) and 6 (+5 V)

6. BAUD RATES: 9.6 Kbaud to 12 Mbaud, Auto Baud Rate Detection
7. STATION ADDRESS: 0 to 125, set by rotary switches
8. SUPPORTED FUNCTIONS:

FREEZE Mode: Supported
SYNC Mode: Supported
FAIL SAFE Mode: Not Supported
EXTERNAL DIAGNOSTIC DATA: Not Supported

9. INSTALLATION REQUIREMENTS:

Installed Depth: 4.88" (124 mm) from the rear of the PAX bezel
Additional Height: 0.35" (9 mm) above the PAX case surface

ORDERING INFORMATION

MODEL NO. DESCRIPTION

PART NUMBER

PAXCDC50

PAXCDC

Bulletin No. PAXCDC5-D
Drawing No. LP0549
Released 01/11

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

CONNECTS PAX METER TO PROFIBUS-DP NETWORK

STANDARD 9-PIN D-SUB CONNECTOR INTERFACE

CYCLIC I/O DATA TRANSMISSION, UP TO 84 BYTES IN/OUT

OPERATING RANGE FROM 9.6 KBAUD TO 12 MBAUD WITH

AUTOMATIC BAUD RATE DETECTION

STATION ADDRESS SET THROUGH ROTARY SWITCHES

CONFIGURATION VIA SELECTION OF PRE-CONFIGURED

MODULES FOR THE SPECIFIC PAX METER TYPE

FREEZE MODE AND SYNC MODE SUPPORTED

DIAGNOSTIC LEDs INDICATE CARD STATUS

PNO CERTIFIED, CONFORMANCE TESTED SLAVE DEVICE

PAX PROFIBUS-DP Communications Card

100

10

1

R0TARY

SWITCHES