Automatic air vent
8.0 Troubleshooting
In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.
If malfunctions cannot be eliminate with the help of the following table
“9.0 troubleshooting table”, the supplier or manufacturer should be consulted.
9.0 Troubleshooting table
-
ATTENTION !
It is essential that the safety regulations are observed when identifying faults.
ATTENTION !
- refer to item 10.0 and 11.0 prior to dismantling and repair work!
- refer to item 6.0 before restarting the plant !
Fault
Possible cause
Corrective measures
No flow
Installed in wrong flow direction
Fit valve in direction of flow arrow.
Flange covers not removed
Remove flange covers
Ball float (Pos. 24.16) defective
Check lifting force; refer to item 7.1
Little flow
Wrong installation position
Note installation position; refer to item
5.5. Correct installation position
Piping system clogged
Check piping system
Wrong controller size choosen
Correct selection acc. to flow diagram
No closure, or internal
leakage
Controller clogged
Clean controller; refer to item 7.1
Controller worn out
Change controller; refer to item 7.1
Controller incorrectly screwed into body
Check seal face between body and con-
troller, tighten controller correctly; refer
to item 7.3
Controller operated above safe operating
pressure
Observe operating limits as per data
sheet, i.e. possibly select different con-
troller
External leakage
Hood (Pos. 16) not properly tightened
cheese-head screw (Pos. 27)
Tighten; refer to item 7.3
Flat gasket (Pos. 17) defective.
Change flat gasket;
refer to item 7.1
Connector (Pos. 45) for venting valve not
properly tightened.
Tighten; refer to item 7.3