6 automatic malfunction message, ari-paco 0,85 y – ARI Armaturen ARI-PACO 0,85kN EN User Manual

Page 27

Advertising
background image

0040506000 1811

Page 27

Operating and installation instructions

Electric thrust actuator ARI-PACO 0,85 kN

6.2.6 Automatic Malfunction message, ARI-PACO 0,85 Y
If during the valve travel a blockage from a foreign body occurs in the pipeline, the drive
notifies this malfunction by means of a feedback signal of approx. 13 V DC (only without
voltage limitation of the Z diode between connector A or 0 possible), on connection terminal
A. Furthermore, the LED beneath the drive housing blinks.
By means of an automatic blockage removal algorithm, the actuating drive next attempts to
free the valve blockage by itself by briefly lifting the valve cone a number of times.
Additional malfunction messages by means of potential-free relay contacts can be made
with the relay card (accessories). The relay card can be retrofitted easily. Refer to Pt. 5.5.3 .

Switch 3
Adjustment of the actuating
direction.
(action direction selection)
Valve open or closed with
actuating signal input 10 V
DC.

Fig. 37

Switch 4
Actuating direction for partial initialization.
In the case of power loss or manual switched usage, the actuating drive carries out a
partial initialization for safety reasons. The direction valve open or valve closed are
determined by the plant conditions.

Servo direction for valve type

switch
position

Control voltage

straight through

3-way

= open

= closed

= flanged