CAUTION: The available gas pressure should be within the limits shown in the

SPECIFICATIONS section. Excessive pressure will damage the Combination Gas Valve and
Regulator. If the supply pressure exceeds the 14.0″ W.C. maximum, a suitable intermediate
main regulator must be installed ahead of the Main Manual Shut-Off Valve shown in Figure 6.

Pipe

Type

Approximate Capacity -MBH

Size

of

Gas

Pipe

Length

10

20 40

75 100

3/4

Natural 200

150

3/4

Propane 590

400 275

190 160

1

Natural 400

275 200

150

1

Propane 1075

730 500

360 300

1 1/4

Natural 900

600 450

325 275

1 1/4

Propane

1040 750 630

1 1/2

Natural

900 650

475 400

1

1/2 Propane

975

-

The burner gas supply piping should branch

off from the main line as close to the gas meter as possible. Do not connect to the bottom of a
horizontal section. Use new black pipe and malleable fi ttings free of burrs.
-

Provide a sediment trap, union and 1/8″ pressure tap in piping close to burner as shown in

Figure 6.
-

Use pipe joint compound approved for use with natural and liquid petroleum gases.

-

Piping must comply with local codes.

-

To obtain the maximum fi ring rate of the burner, the fuel gas supply piping must be sized to

provide a minimum of 6″ W.C. pressure to the inlet of the combination valve when the burner and all
other gas appliances are on.
-

When pressure testing the supply piping, the burner valve train must be protected.

CAUTION: If the test pressure is 0.5 PSIG or less, closing the Main Manual Shut-Off

Valve will suffi ce.

DANGER: Explosion hazard.

Do

not

use

oxygen

for

pressure

testing.

An explosion could occur during initial start-up.

-

If the burner piping must be rearranged because of space limitations, be sure to carry out

the general arrangement shown in Figure 6. The Combination Gas Valve will operate and can be
installed in any position except up-side down.
-

When the burner is installed in jacketed equipment, it is recommended that the Combination

Gas Valve be left adjacent to the burner within the vestibule. The Main Manual Shut-Off Valve can
be installed outside of the jacketed equipment.

___________________________

The EC200 and EC300 burners are approved for use with NATURAL or PROPANE gas only, and
should be used only with the gas specifi ed on rating plate.
-

A Standard Model EC Series Economite is shipped ready for NATURAL gas and is fi eld

convertible to PROPANE gas, see Table 3.
-

As shipped, the EC200 has no spud installed, manifold pressure set at 4.1″ W.C., air restrictors

off and the air shutter full open. As shipped the EC 300 has no spud installed, manifold pressure set
at 4.0″ W.C., air restrictors off and the air shutter full open. OEM applications will be set based on
the equipment requirements.
-

If the required fi ring rate does not fall within the range of the installed orifi ce, or if converting

to PROPANE gas, use Table 3 to select the spud with the correct orifi ce size (stamped in inch
diameter) for the desired capacity from the spare orifi ce bag assembly.
-

To change the orifi ce, turn off the Main Manual Shut-Off Valve and the main electric to the

burner Refer to piping diagram, Figure 6, to locate the orifi ce location if required.

Part 1 Installation

VI - Piping

EC 200 / 300

INSTALLER PROVIDED
SEDIMENT TRAP

INSTALLER PROVIDED UNION

INSTALLER PROVIDED
1/8" NPT PRESSURE TAP
IN SUPPLY PIPING

INSTALLER PROVIDED
SHUT OFF VALVE

REMOVE PLUG -
ORIFICE IS
LOCATED INSIDE

Capacities shown are for a total pressure drop of 0.3W.C.

For 0.5W.C. pressure drop, multiply capacity shown by 1.3.

Propane capacities shown are for a total pressure drop of 0.5

W.C. For higher permissible pressure drops, consult your gas

supplier.

Table 2: Schedule 40 NPT Pipe-Capacity Chart

Figure 6: Piping Connections