Part 2 Service & Part 3 Maintenance

Special equipment, either factory or contractor installed, may cause variation in the
procedures and descriptions given in this manual.

Consult the OEM's manual to identify the differences in the information.

____________________________________________

The major difference for the CUL version of the RE4850BA, RE4700BA, RE4400BA and
RE4400B is the French / English specification plate, French / English manual and the firing
valve for the pilot line.

____________________________________________

CONSUMER INSTRUCTIONS

Keep the area around the burner clear and free of combustible material, gasoline or other

flammable liquids or vapors. Do not obstruct burner air openings or ventilation grills for
combustion air.

The motor features permanently lubricated ball bearings and requires no maintenance.

WARNING: If any flame is observed when the burner is on standby, or if the

ignition spark or valve operator is heard to come on before the motor reaches
operating speed, immediately turn off the manual gas control and burner power. A
dangerous condition has developed and must be corrected. CONTACT A QUALIFIED
SERVICE TECHNICIAN FOR CLEANING, READJUSTMENT OR REPAIR.

Check that the pilot ignition spark does not come on before the motor reaches operating

speed. If it does, the air switch is defective and must be replaced. (See Section X, Motor /
Blower Interlock).

____________________________________________

LIGHTING INSTRUCTIONS

1.

SET OPERATING CONTROL TO OFF OR THERMOSTAT BELOW ROOM
TEMPERATURE.

2.

TURN MANUAL GAS COCK ON.

3.

TURN BURNER POWER ON.

4.

SET OPERATING CONTROL TO ON OR THERMOSTAT TO CALL FOR
HEAT.

5.

IF THE PILOT FLAME IS NOT PROVEN WITHIN 15 SECONDS, AFTER THE
PRE-PURGE, THE IGNITION CONTROL MODULE WILL SHUT OFF THE
AUTOMATIC SAFETY SHUT-OFF VALVES AND LOCK OUT. IF THE PROOF
OF FLAME IS LOST DURING BURNER RUN AND THE PILOT IS NOT RE-
ESTABLISHED WITHIN15 SECONDS AFTER THE PRE-PURGE, THE
PRIMARY SAFETY CONTROL WILL SHUT OFF THE AUTOMATIC SAFETY
SHUT-OFF VALVES AND LOCKOUT. TO RESET FOR RESTART, DE-
ENERGIZE THE CONTROL BY SETTING THE OPERATING CONTROL TO
OFF OR THERMOSTAT BELOW ROOM TEMPERATURE FOR AT LEAST 60
SECONDS.

6.

REPEAT STEP 4 FOR RESTART.

TO SHUT OFF
1.

TURN MANUAL GAS COCK OFF.

2.

TURN BURNER POWER OFF.

SHOULD OVERHEATING OF THE APPLIANCE OCCUR
1.

Shut off the manual gas control to the appliance.

2.

Do not shut off the electrical supply power to the blower.

14

Part 3

Maintenance

Lighting Instructions

XVIII

Special

Equipment

(OEM Versions)

XIX

Canadian

Specifications